Document Part # 026-4842 Rev 1
Page 3 of 4
©2017 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
2. When Setup mode is entered, the
Menu
LED blinks red and the
Set
LED blinks green.
3. Select
1 Hop
by quickly pressing the
Set
button twice and the
Set
LED will blink amber twice, or select
2 Hops
by quickly
pressing the
Set
button three (3) times and the
Set
LED will blink amber three times.
4. To exit Advanced Setup Mode and return to normal operation, press and hold both buttons for
two (2) seconds and both LEDs will blink green to confirm.
Link a 3rd Party Transmitter to a Repeater
Note: If an Emerson Module or Sensor is being used, the Repeater automatically links to the device and repeats the transmission once it
is powered up and configured.
1. To access Basic Setup Mode, press and hold both buttons for two (2) seconds until both LEDs are green.
When the Repeater is ready to accept a link, both LEDs blink once per second.
Note: Once activated, this option stays active for two (2) minutes to provide time to link multiple devices.
2. For the transmitter to be linked to the repeater, press the
Link
button on that device. The Module is linked successfully
when the
Set
LED displays solid green for three (3) seconds.
Option
Description
1 Hop
More than 20 Transmitters near a Repeater
2 Hop
Less than 20 Transmitters near a Repeater