Designing a Liebert XD Solution
26
3.16 Determining Refrigerant Volume
After the preliminary system design is completed,
Tables 7
, through
15
may be used to determine
the amount of refrigerant required. Perform the calculation below for each Liebert XD system being
configured.
3.16.1 Liebert XDP/Liebert XDC Pumped R-134a Circuit Volume
NOTE
All lengths in
Tables 7
,
8
,
9
and
10
,
are actual pipe lengths, not equivalent pipe lengths.
NOTE
System refrigerant volume calculations in
Tables 7
,
8
,
9
and
10
,
are based on a fully loaded
system. Additional charge may be required for lightly loaded systems.
Table 7
System R-134a charge for a Liebert XDP/Liebert XDC with any model Liebert
XDH/Liebert XDO/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb (kg)
Per Liebert XD Unit
(Excludes Connector Lines
to and from Liebert XD Cooling Module)
157 lb. (65.7kg)
Liebert XDP/Liebert XDC
3.55 lb. (0.66kg)
Liebert XDO
2.32 lb. (1.05kg)
Liebert XDV
5.32 lb. (2.41kg)
Liebert XDH
1.41 lb. (0.64kg)
Liebert XDCF
Table 8
System refrigerant charge for the supply and return mains
Refrigerant Charge,
lb/foot (kg/m)
Supply/Return Main Length and Diameter
0.45 (0.67)
Main supply actual length per 1-1/8" OD copper tubing
0.68 (1.01)
Main supply actual length per 1-3/8" OD copper tubing
0.28 (0.42)
Main return actual length per 2-1/8" OD copper tubing
0.43 (0.64)
Main return actual length per 2-5/8" OD copper tubing
Table 9
R-134a refrigerant charge for hard-piped connector lines to and from any model
Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb/foot (kg/m)
Hard-Piped Connector Length and Diameter
0.08 (0.12)
1/2" OD Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF supply connector
actual length
0.13 (0.19)
5/8" OD copper tubing Liebert XDV/Liebert XDCF supply connector actual length
0.26 (0.39)
7/8" OD Liebert XDO/Liebert XDH supply connector actual length "
0.02 (0.03)
5/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length
0.04 (0.06)
7/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length
0.04 (0.06)
7/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length
0.07 (0.1)
1-1/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length