![Emerson 189192G3 Скачать руководство пользователя страница 70](http://html.mh-extra.com/html/emerson/189192g3/189192g3_design-manual_100916070.webp)
Specifications
64
5.0
S
PECIFICATIONS
Table 27
Liebert XDC160 specifications
Models
XDC160 Air
XDC160 Water /
Glycol
XDC160AA
XDC160AM
189192G3
189192G5
Cooling Capacity, tons (kW)
46 (160)
37 (130)
See
Tables 28
,
29
and
30
for
Water/Glycol
performance data
Minimum Load
The Liebert XDC’s minimum recommended operating load is 40% of
system nominal capacity. For example, a Liebert XDC160 60Hz
system’s minimum load would be 64 kW. Loading below this value
can unfavorably affect system operation. Consult factory for any
loading below this recommendation.
Electrical Requirements
Input
460V-3ph-60Hz
380/415V-3ph-50Hz
460V-3ph-60Hz
Full Load Amps
79A
Minimum supply wire sizing ampacity
84A
Maximum fuse or circuit breaker size
100A
Dimensions, inches (mm)
Height - Main unit only
78 (1981)
Height - Main unit only, as shipped
83 (2108)
Width - Main unit
74 (1879)
Depth - Main unit
34-5/8 (879)
Height - Water / Glycol cooled condenser stand
N/A
24 (607)
Width - Water / Glycol cooled condenser stand
N/A
72 (1829)
Depth - Water / Glycol cooled condenser stand
N/A
33 (839)
Weight, lb (kg)
Main unit only
1800 (817)
Main unit only, as shipped
Domestic: 1945 (882); Export: 2093 (949)
Water / Glycol cooled condenser stand
N/A
1075 (488)
Water / Glycol cooled condenser stand, as shipped
N/A
1150 (521)
Pipe Connections, inches, O.D., Cu
Liebert XD Coolant supply to XD cooling modules
1-1/8
Liebert XD Coolant return from XD cooling modules
2-1/8
Liquid line, DX circuit
7/8
Hot gas line, DX circuit
1-3/8
Heat Rejection Equipment
95°F ambient air cooled condenser
1-CDL830 or 2-CSL415
N/A
Number of XD Cooling Units Connected, Maximum (Minimum)
Liebert XDCF10
16 (6)
Liebert XDH20
8 (4)
Liebert XDH32
5 (2)
Liebert XDO16
10 (4)
Liebert XDO20
8 (4)
Liebert XDV8
20 (8)
Liebert XDV10
16 (7)
Cabinet Exterior Finish
Black, matte finish, heat-fused powder coat
Maximum Ambient Operating Temperature °F(°C)
86 (30)
Agency
Approvals
CSA
CE
CSA