Description of Operation 

The Phone Line Monitoring (PLM) feature built into the EmerCom EMC-60 Hands-free 
Elevator Phone monitors the phone line as required by ASME A17.1/CSA B44 Code. If 
the phone line fails a pair of contacts in the EMC-60 will open (fail-safe) to signal the 
EMC-ALRM Alarm Annunciator to generate an audible & visual alert in the elevator 
lobby, in the vicinity of the Firefighters Recall Switch. 

The visual alert LED will flash until the phone line becomes operational again but the 
audible alert buzzer can be silenced by authorized personnel with the key switch (or 
pushbutton accessible only to authorized personnel). The buzzer will remain silenced 
for 12 hours unless the phone line is restored earlier. 

Three LEDs mounted on the EMC-ALRM PCB indicate ‘normal’, ‘alarm’ or ‘silenced’ 
status. 

A PLM test feature is available in the EMC-60 phone to simulate an alarm by opening 
the relay contacts for the number of seconds entered (Command # 24), after which it 
returns to normal. An extended test can be conducted by moving the test switch on the 
EMC-ALRM PCB into the “TEST” position. 

For 

High-Rise

 installations an EMCS Consolidator or Rescue Station will be required to 

call into any cab from an on-site location. The EMCS Consolidator regularly checks the 
health of the external phone lines and the connection with all of the EMC-60 Phones 
and sends a signal to the EMC-ALRM (connections to the EMC-60 phone PLM 
terminals are not required with the EMCS). 

 

Troubleshooting 

EC-Phone indicates a phone line fault but no alarm triggered

 

  Check 12-24V DC supplied and polarity correct 

  Ensure additional EMC-60 phones are connected in series 

EC-Phone indicates phone line okay but alarm triggers

 

  Verify the test switch is in the “NORMAL” position 

  Check wiring for open-circuits. 

Buzzer is not loud enough 

  Ensure the sticker has been removed from the buzzer 

 

Содержание EMC-ALRM

Страница 1: ...EMC ALRM USER GUIDE Phone Line Monitoring System EMC 60 Hands Free Phone EMC ALRM Board...

Страница 2: ...lect the test time in seconds and touch For High Rise test Disconnect phone line to the CAB at the EMCS Try calling the cab for quick test to verify alarm Reconnect to reset then repeat but wait for a...

Страница 3: ...s the operability of the telephone line and signals the EMC ALRM if the line is not functional In the event of a phone line failure the EMC ALRM activates an audible and illuminated visual signal for...

Страница 4: ...line 12 24 V DC power EmerCom EMC 60 Hands Free Elevator Phone EmerCom EMC ALRM Board from other EMC 60 phones in the group for Low Rise w o EMCS An EMC PAC Battery backed up Power Supply and Connecto...

Страница 5: ...uide 5 EMC PAC and EMC ALRM Low Rise Layout Group B Group A Telco Phone Line EMC PAC 110 V AC EMC 60 Hands free phones in elevator cabs EMC ALRM EMC ALRM Shielded Twisted Pair STP battery 110V Supply...

Страница 6: ...de 6 EMCS and EMC ALRM High Rise Layout Group B Group A Phone lines EMCS 110 V AC EMC 60 Hands free phones in elevator cabs Security Desk EMC ALRM EC MR s Shielded Twisted Pair STP Shielded CAT 5 110V...

Страница 7: ...eature is available in the EMC 60 phone to simulate an alarm by opening the relay contacts for the number of seconds entered Command 24 after which it returns to normal An extended test can be conduct...

Страница 8: ...or in a manner other than that for which they were manufactured will void the warranty Please return defective products prepaid to your nearest service center after first calling 1 604 589 3899 or to...

Отзывы: