Emerald EE-HWS-SSHP-200 Скачать руководство пользователя страница 9

MANUAL DEFROSTING MODE

1.   In the main interface, Press the buttons “M” + “

” simultaneously for 

more than 5 seconds to activate or deactivate the Defrost mode. 

2.   If the defrosting mode is activated, the icon 

 will be displayed. 

Please note defrosting mode will not work if heat pump is in  

cooling mode.

QUERY SYSTEM RUNNING STATUS

1.   In the main interface, no matter if the system is ON or OFF, press 

the button “

” or “

” for more than 3 seconds to enter the running 

status query interface.

2.  Press the button “

” or “

” to check each of the following codes.

3.   Click the button “

” or no operation for more than 30 seconds, 

the controller will return to the main interface.

4.   After entering the view mode, the last viewed code (the default is 

“00” after power-on) and its corresponding value are displayed. 

5.  Click the button “

” the following code table can be displayed in order:

DESCRIPTION

CODE

Remark

Gas cycle/water cycle 

00

0=water cycle, 1=gas cycle 

(Dynamic/X8)

High pressure switch

01

0=open, 1=close

Low pressure switch

02

0=open, 1=close

Water flow switch

03

0=open, 1=close

EEV value

04

Real instant detected value

Evaporator coil sensor

05

Real instant detected value

Ambient temperature sensor

06

Real instant detected value

Suction temperature sensor

07

Real instant detected value

Exhaust temperature sensor

08

Real instant detected value

Tank water temperature

09

Real instant detected value

Returned water temperature)

10

Not for Dynamic/X8

Compressor

11

0=OFF, 1=ON

4-way valve

12

0=OFF, 1=ON

High-speed of fan

13

0=OFF, 1=ON

Low-speed of fan

14

0=OFF, 1=ON

Circulation water pump

15

0=OFF, 1=ON (Not for Dynamic/

X8)

Electric heating element

16

0=OFF, 1=ON

Compressor running time before 

defrost

17

Real accumulated time

Back-up linked switch

18

0=open, 1=close

Programme version

19

Show real version No.

MANUAL STERILIZATION

1.   If the controller is in the normal display state and it is currently  

in the heating mode, press the “M”+“

”+“

” button at the same 

time for more than 5 seconds to activate or deactivate the  

“sterilization” function. The "

" is flashing under manual  

“sterilization” operation. 

2.   When heat pump is in cooling mode, "sterilization" operation is  

not allowed.

CONTROLLER BUTTON LOCK

All buttons will be locked if there is no button operation for more than 

60 seconds. Click any button to unlock.

ERROR CODE

1)  “E09” is displayed when the communication between the main 

board and controller is abnormal, or the data line is not connected 

normally. 
2)  “--:--” is displayed when the valid clock cannot be obtained, and 

the communication indicator of the main control board flashes. The 

buzzer sounds when an alarm occurs. Press any key to silence the 

alarm.
3)  Please see the following detailed error code table:

ERROR 
CODE

DESCRIPTION

E01

Water flow switch disconnected (water cycle heat pump)

E02

Exhaust temperature too high

E03

High-pressure switch failure

E04

Low-pressure switch failure

E09

Communication failure between controller and main board

E11

Evaporator coil temperature sensor failure

E12

Ambient temperature sensor failure

E13

Exhaust temperature sensor failure

E14

Water inlet temperature sensor failure

E15

Tank temperature sensor failure

E17

Absorb temperature sensor failure

E18

Water outlet temperature sensor failure

E19

Return water temperature sensor failure

E20

Outlet water temperature too high protection (water cycle heat 
pump)

E21

Outlet water temperature too low protection (water cycle heat pump)

CONTROLLER INSTRUCTIONS

Содержание EE-HWS-SSHP-200

Страница 1: ...d Energy This leaflet contains important information on the correct installation and operation of your heat pump water heater PACKING LIST 1 User manual 1 Heat pump unit 1 Water tank unit 1 TPR valve...

Страница 2: ...ments 6 Electrical work must be insulated and compliant with electrical technical standards 7 The unit must be powered for 3 4 hours before use INSTALLATION SPACE 1 Check space for maintenance before...

Страница 3: ...inlet and outlet pipe for hanging Refer to the Hoisting Heat Pump diagram PLUMBING CONNECTION Connecting water inlet and outlet pipes To house Hot water To drain Cold water Control panel Water temper...

Страница 4: ...0mm female thread 2 The hot water supply should be connected to a 20mm socket 3 To ensure thermal efficiency all hot water lines and connections must be insulated with a minimum 13mm closed cell insul...

Страница 5: ...nection Wiring must be conducted by a professional installation technician in accordance with the circuit diagram The power and signal line layout should be neat and not in contact with each other or...

Страница 6: ...Display Timer mode ECO mode Constantly bright In the range of timer period Flashing Set starting time for timer mode Constantly bright Out of the range of timer period Flashing Set ending time for ti...

Страница 7: ...inspection of controller screen System is OFF make sure the system connects with power supply less than 5 minutes before operation Press all 4 buttons simultaneously for 5 seconds to restore the fact...

Страница 8: ...y ELECTRIC HEATER CONTROL BOOSTER MODE 1 To turn on off electric heating element Press both buttons simultaneously for more than 3 seconds 2 The electric heating element will heat the water to the set...

Страница 9: ...ng element 16 0 OFF 1 ON Compressor running time before defrost 17 Real accumulated time Back up linked switch 18 0 open 1 close Programme version 19 Show real version No MANUAL STERILIZATION 1 If the...

Страница 10: ...sorb temperature sensor and outlet water temperature sensor return water temperature sensor are faulty CONTROLLER INSTRUCTIONS THE ALARM LOW PRESSURE FAULT 1 If the compressor starts running for 5 min...

Страница 11: ...red Regularly check the reliability of the electrical components Change any faulty or unreliable components After a long period of operation there will be a build up of calcium oxidized or other miner...

Страница 12: ...d inlet or compressor suction pipe is blocked expansion valve unadjusted or failed The refrigerant is not enough in the sytem Adjust suitable overheat temperature examine whether there is Fluo rine le...