ANTIFREEZE PROTECTION 

1.   When the controller is on and the ambient temperature is too low 

it will enter the antifreeze mode to prevent the circulation line or 

the water tank from freezing.

2.   When the ambient temperature is ≤ 2

°C

, the heat pump enters the 

first anti-freeze protection. The circulating water pump continuous-

ly stops for more than 30 minutes, then starts for 60 seconds, and 

repeats the cycle.

3.   When the ambient temperature is ≤ 2

°C

, and the water tank 

temperature is ≤ 5

°C

, heat pump enters the secondary anti-freeze 

protection when the heat pump automatically turns on for heating. 

When the ambient temperature ≥ 4

°C

 or the tank temperature is  

≥ 15

°C

, the heat pump stops heating and exits the secondary frost 

protection.

LOW AMBIENT TEMPERATURE PROTECTION

1.   When the ambient temperature is ≤ -9°C, the compressor will not 

operate. 

2.   When the ambient temperature is ≥ -7°C normal operation is 

resumed. This protection has no fault display.

WATER TEMPERATURE OVERCOOLS AT COOLING MODE

1.   If the compressor is running for 5 minutes in the cooling mode 

and the outlet water temperature is < 5°C for 5 consecutive  

seconds, the heat pump enters sub cooling protection. The  

compressor and the fan will stop running, and the water pump  

will operate as normal. 

2.   When the outlet water temperature is detected to be ≥ 7 °C, the 

heat pump exits the sub cooling protection and will operate as 
normal.

WATER TEMPERATURE OVERHEAT PROTECTION AT HEATING 

MODE 

1.   If the compressor is running for 5 minutes in the heating mode 

and the water temperature is  ≥ 65°C for 5 consecutive seconds,  

it is judged that the outlet water temperature is too high. It will shut 

down heat pump for protection. 

2.   When the outlet water temperature is deteced to be ≤ 60°C, the 

heat pump exits the sub heating protection and will operate as 

normal.

TEMPERATURE SENSOR FAILURE

1.   The heat pump will stop if the water tank temperature sensor, outlet 

water temperature sensor, or ambient temperature sensor is faulty. 

2.   The electric heater will continue to operate if the exhaust,  

evaporator coil or water return temperature sensor is faulty. 

3.   When the return water temperature sensor fails, the return pump is 

allowed to run (the return water temperature will not be accurate)

4.   The electric heater will not operate if the water tank or ambient 

temperature sensor are faulty.

5..  “11E”, “12E”, “13E” ", "14E", "15E", "17E", "18E", "19E". correspond  

with the following faults: coil temperature sensor, ambient  

temperature sensor, exhaust temperature sensor, inlet water 

temperature sensor/tank temperature sensor, absorb temperature 

sensor, and outlet water temperature sensor/return water  

temperature sensor are faulty. 

CONTROLLER INSTRUCTIONS

THE ALARM

LOW PRESSURE FAULT

1.   If the compressor starts running for 5 minutes and the low- 

pressure switch is off for 10 consecutive seconds the compressor 

immediately stops running. At this time the controller will display 

the low-pressure fault alarm code “04E”. If the low-pressure switch 

is restored the error code does not occur. If no other protection or 

locking occurs, the compressor will restart after 3 minutes.

2.   If low-pressure fault protection appears 3 times within 1 hour, the 

controller will lock the protection. The compressor will lock in the 

shutdown protection state. At this time, only the shutdown and 

restarting can unlock the compressor. The low-pressure switch is 

not detected during the defrosting.

HIGH PRESSURE FAILURE

1.   If the compressor starts running and the high-pressure switch is 

off for for 10 consecutive seconds the compressor immediately 

stops running. At this time the controller will display the high- 

pressure fault alarm code “03E”. If the high-pressure switch is 

restored, error code will not occur. If no other protection or  

locking occurs, the compressor will restart after 3 minutes.

2.   If high-pressure fault protection appears 3 times within 1 hour, 

the controller will lock the protection, and the compressor will 

be locked in the shutdown protection state. At this time only the 

shutdown and restarting can unlock the compressor. 

HIGH EXHAUST TEMPERATURE FAILURE

1.   If the compressor starts running for 1 minute and the exhaust  

gas temperature is detected to be higher than, or equal to the  

exhaust high temperature protection value by 110

°C

 for 10  

consecutive seconds, a high exhaust temperature alarm will 

sound and the compressor will stop. At this time, controller  

shows high temperature fault alarm code "02E". When the  

exhaust temperature drops back to 90

°C

, the alarm is released 

and the normal temperature control function is restored.

2.   If high temperature fault protection appears 3 times within half an 

hour, the controller will lock the protection, and the compressor 

will be locked in the shutdown protection state. At this time only 

the shutdown and restarting can unlock the compressor. 

WATER FLOW FAILURE 

1.   If the circulating water pump starts and the water flow switch is off 

for 10 seconds then heat pump will stop. At this time, the controller 

displays the water flow switch fault alarm code “01E”. 

2.  Periodically (1 minute) restarts the water pump and 10 seconds  

later, the flow switch is detected. If water flow switch is closed, 

heat pump will operate normally. If the fault occurs 3 times within  

1 hour, the fault is locked and heat pump will not start. 

Содержание EE-HWS-SSHP-200

Страница 1: ...d Energy This leaflet contains important information on the correct installation and operation of your heat pump water heater PACKING LIST 1 User manual 1 Heat pump unit 1 Water tank unit 1 TPR valve...

Страница 2: ...ments 6 Electrical work must be insulated and compliant with electrical technical standards 7 The unit must be powered for 3 4 hours before use INSTALLATION SPACE 1 Check space for maintenance before...

Страница 3: ...inlet and outlet pipe for hanging Refer to the Hoisting Heat Pump diagram PLUMBING CONNECTION Connecting water inlet and outlet pipes To house Hot water To drain Cold water Control panel Water temper...

Страница 4: ...0mm female thread 2 The hot water supply should be connected to a 20mm socket 3 To ensure thermal efficiency all hot water lines and connections must be insulated with a minimum 13mm closed cell insul...

Страница 5: ...nection Wiring must be conducted by a professional installation technician in accordance with the circuit diagram The power and signal line layout should be neat and not in contact with each other or...

Страница 6: ...Display Timer mode ECO mode Constantly bright In the range of timer period Flashing Set starting time for timer mode Constantly bright Out of the range of timer period Flashing Set ending time for ti...

Страница 7: ...inspection of controller screen System is OFF make sure the system connects with power supply less than 5 minutes before operation Press all 4 buttons simultaneously for 5 seconds to restore the fact...

Страница 8: ...y ELECTRIC HEATER CONTROL BOOSTER MODE 1 To turn on off electric heating element Press both buttons simultaneously for more than 3 seconds 2 The electric heating element will heat the water to the set...

Страница 9: ...ng element 16 0 OFF 1 ON Compressor running time before defrost 17 Real accumulated time Back up linked switch 18 0 open 1 close Programme version 19 Show real version No MANUAL STERILIZATION 1 If the...

Страница 10: ...sorb temperature sensor and outlet water temperature sensor return water temperature sensor are faulty CONTROLLER INSTRUCTIONS THE ALARM LOW PRESSURE FAULT 1 If the compressor starts running for 5 min...

Страница 11: ...red Regularly check the reliability of the electrical components Change any faulty or unreliable components After a long period of operation there will be a build up of calcium oxidized or other miner...

Страница 12: ...d inlet or compressor suction pipe is blocked expansion valve unadjusted or failed The refrigerant is not enough in the sytem Adjust suitable overheat temperature examine whether there is Fluo rine le...

Отзывы: