14
8.1 “Set-Point”, pH (proportional)
pH reading values can be set to operate the pH pump using 2 set-points into
On/Off mode or Proportional (%).
Proportional mode set the instrument to operate using a calculated percentage between two set values that
enable or disable the pH pump. To use this mode move cursor on “Working Mode”. Press the wheel and select it.
PROPORTIONAL mode between 7pH(0%) and 8pH (100%). [Stroke setting 180]
In this mode the pH pump will be “ON” for values greater than 8pH with maximum set strokes capacity (e.g.: 180) and
it’ll be “OFF” for values lower than 7pH. For values of 7.5pH pump will be “ON” with 90 strokes capacity. The calculation
is based on 180 strokes setting (see page 22). To end procedure move cursor on “OK” and press wheel to proceed to
“Save” request screen. Move wheel on “YES” to save or “NO” to discard changes.