Chapter 2 Hardware Installation
2-7
Figure 2-4: Installing the BBU Module
2.7 Hard Drive Installation
2.7.1 Hard Drive Installation Prerequisites
CAUTION!
The hard drives and drive trays should only be installed into the
subsystem after the subsystem has been mounted into a rack cabinet. If
the hard drives are installed first, the subsystem will be too heavy to
handle and the possible impact during installation may damage your
drives.
WARNING!
Handle hard drives with extreme care. Hard drives are very delicate.
Dropping a drive against a hard surface (even from a short distance)
and hitting or touching the circuits on the drives with your tools may
cause damage to the drives.
WARNING!
All drive trays must be installed into the enclosure even if they do not
contain a hard drive. If the trays are not installed into the enclosure, the
ventilation airflow will not be normalized and the subsystem will overheat.
2.7.2
Hard Drive/Drive Tray Installation
Step 1.
Make sure
the rotary bezel lock is in the unlocked
position
, i.e., the groove on its face is in a horizontal
orientation. If the groove is in a vertical position, as shown
Formatted: Bullets and Numbering