Examples
Example 1:
Parameter
Value
Readout interval
60
Transmit interval
1440 (daily)
Message encoding
SenML/CBOR/M-Bus version 0
Message format
Standard
Max transmissions per day 3
This example results in the transmission of one message per day, containing 24 readings, all with the
contents defined in the Standard message format. Data is encoded using SenML/CBOR/M-Bus.
Maximum 3 unsent such messages are sent each time (if for some reason the messages were not sent
“last time”). So maximum transmitted messages per day is 3 (containing 3x24=72 readings, covering 3
days)
Example 2:
Parameter
Value
Readout interval
120
Transmit interval
720
Message encoding
SenML/CBOR/M-Bus version 0
Message format
Tariff
Max transmissions per day 2
This example results in the transmission of one message every 12h, containing 6 readings, all with the
content defined in the Tariff message format. Data is encoded using SenML/CBOR/M-Bus. Maximum 2
unsent such messages are sent each time (if for some reason the messages were not sent “last time”),
so maximum transmitted messages per day is 4 (containing 4x6=24 readings, covering 2 days).
7.5
Configuration options
CMi6110 is configured via preconfigure service at delivery, via LwM2M device management or via the
Elvaco OTC App, using NFC to transfer settings to the module. The Elvaco OTC App is downloaded via
Google Play or at App Store for iOS. When the application has been installed, you can log in by using the
user symbol in the top right corner. This will give you access to all your configuration profiles and enable
you to configure any locked devices that have been claimed to your account.
Table 8 through Table 12. provides a summary of all readable/writeable settings in CMi6110. Please note
that the default configuration below is the one tailored for optimizing the performance of battery powered
units. If changing these settings, the stipulated battery lifetime cannot be guaranteed.
Device related configurations available in CMi6110:
Parameter
Description
Configurable
values
Default
value
(battery)
Device access
–
Locked device &
correct PAK
or
open device
Device access
–
No PAK
Meter ID
Meter identification
(secondary ID) for
L+G UH50/UC50
N/A
N/A
Readable
Readable
Power mode
Activation status of
the module.
Passive, Active
Passive
Readable/
Writeable
Readable
Configuration
Lock
Locks the module to
prevent unauthorized
access.
Open, Locked
Open
Readable/
Writeable
Readable