P02 – Pump operation time setting
Shows current pump operating time,
increase operating time,
decrease operating time,
confirm setting (10 is recommended), ON parameter on display sets continuous pump operation
independently of boiler heaters operation status,
go to P03 function.
P03 – PID controller
Shows current PID setting,
increase coefficient
decrease coefficient,
confirm setting (3 is
recommended),
go to P04 function.
Note: if it takes too long for boiler to reach required temperature,
set coefficient on 4 or 5 and to 1 or 2 if the increase is too fast.
P04 – Maximum boiler operating temperature - CH
Shows set operating temperature,
increase temperature up to 70°C (90°C for AsHZ and ASBIII only),
decrease temperature,
confirm setting (70 is recommended),
go to P05 function.
P05 – Maximum boiler operating temperature – HUW (AsD model only)
Shows set operating temperature,
increase temperature up to 65°C,
decrease temperature
down to 5°C,
confirm setting (50 is recommended),
go to P06 function.
P06 – Boiler operation hysteresis
Shows current hysteresis setting,
increase value 2-6°C
decrease value 5-1°C,
confirm setting
(6 is recommended),
go to P07 function.
Note: 1-2-3°C setting is available with max temperature of
40°C; 4-5-6°C setting is available with temperatures between 50 and 90°C.
P07 – Energy consumption in kWh
(for preset time not exceeding 24h, after 24h counter stops)
Shows consumption level in kWh,
counter resets, kWh consumption level is calculated with 1
second updates,
go to P08 function.
P08 – Energy consumption in kWh for the last 24 hours
LED display shows consumption level in kWh for the last 24h with 20 minutes updates,
go to P09
function.