27
Start Meter /
Stop Meter
Load table with received data
Edit Chan
Click over a channel, click Edit Channel to
edit. (Use to accept a transmitter not
available for direct connection.)
Clear Chan
data
Click over a channel, click Clear Channel
data
Set Nbr
Chans
Enter Number of channels to display (160
maximum) and click Set Nbr Chans to
confirm (this reduces unnecessary on
screen information and speeds up the
interface).
11.2
Channel Set-up Procedure
Transmitter present:
•
Start up the Configuration program. (If this is the first time it has run
you will need to configure the serial port(s) using
File > Properties
.)
•
Connect the PC to the RC250 using the LC68 programming lead (and
USB converter if required)
•
Get the current or start a new RC250 Configuration using the
Get RX
button ( you should see the details appear in the right hand list box).
•
1
Now connect each transmitter to the PC using an LC-TX3*
programming lead.
•
Use
File > Properties
to set the TX serial port.
•
Get the transmitter details using the Get TX button (the TX serial
number will appear)
•
Set the transmitter interval. This should be about one sixth of the
update interval required in the PC (or connected monitoring device)
•
Click on a channel, click
Select Range
, and choose input type from
drop down. Click
OK
to confirm.
•
Repeat for channels applicable to connected TX
•
Repeat if a number of transmitters are being added to the RC250
•
Connect the PC to the RC250 using the LC68 programming lead
•
Select the destination RC250 channel (by single clicking and
highlighting it)
•
Select the required transmitter channel (by single clicking and
highlighting it).
•
Copy the channel details to the RC250 configuration using the >>
button. Note RxConfig will assume the next TX channel and next RX
channel are to be linked. Click the >> button to confirm or set up as
required. To set up another TX, go back to the
1
Now connect… step.