DC/DC Converter 

PSC30 

User Manual 

Page 9 (24) 

 

©2009. ELTEK VALERE DEUTSCHLAND GmbH.   

UM_PSC30_E_EVD_2011-01-19.doc 

 

5.3 Monitoring 

 

5.3.1   Mains voltage monitoring 

 

Mains voltage monitoring; signaling with LED "Mains", criterion: output voltage of step-up-converter 

 370 V, at the same time operation monitoring of step-up-converter (equivalent to main voltage of 

approx. 

 195 (100)V DC; depending on the load). 

The LED is dark if mains voltage low or the step-up-converter is out of order. 
This signal is included in the collective failure signal. Additional there is an optocouppler signal 
(mains O.K.)  
 

5.3.2 Operation 

monitoring 

 
Functional monitoring; signaling by LED "V

O1

", criterion: output voltage 

 97 % of the adjusted output 

voltage 

without

 constant current regulation; 

 85 % of the adjusted output voltage 

with

 constant 

current regulation. The signaling threshold of this monitoring follows the adjusted nominal output 
voltage automatically. 
This signal is included in the collective failure signal of the module. Additional there is an optocoup-
pler signal (V

O

 O.K.) 

At operation with internal decoupling diodes the voltage before diodes will be measured. 

 
5.3.3   Output voltage low 

 
Output voltage low monitoring; signaling by LED "V<",  
criterion: output voltage is higher than adjusted level V<; 
This signal is included in collective failure signal. It has its own relay contact on signaling connector 
too. If the voltage value is okay, Pin 13 and Pin 17 of X2 or Pin 11 and Pin 15 of X4 (220V  output 
voltage) are closed.  
 

5.3.4  Output voltage high 

 
Output voltage high monitoring; signaling by red LED "V>",  
criterion: output voltage higher than adjusted level V>. This signal is included in the collective failure 
signal of the SMPS. If there is an error the LED glows and the SMPS switches off internally. This pro-
tective equipment has an automatic locking and should be reset by the mains switch or remote 
ON/OFF. 

 
5.3.5  Protection against overheating 

 
Protection against overheating; signaling by red LED "Alarm", criterion: temperatur of heat sink > 
90°C. The over temperature protection switches OFF the SMPS when the limited temperature value 
is attained. 
This signal is included in the collective failure signal. You have to reset the unit by ON/OFF switch. 
 

5.3.6  

Signals 

 
The signals "V

O

 O.K.", "Mains O.K." and "Constant Current Mode I

const

" are opto coupler signals with a 

loading of 30 V/5 mA. The opto couplers switch off at error. The collective failure signal is delayed 
for approx. 10 sec. The relay contacts between Pin 14 and Pin 15 of X2 (24/48/60/110V output 
voltage) and Pin 12 to Pin 13 of X4 (220V output voltage) are open and between Pin 15 and Pin 16 
(X2:24/48/60/110V), and Pin 13/14 (X4:220V) are closed at error. 
 
 

Содержание PSC30

Страница 1: ...DC DC Converter PSC30 User Manual UM_PSC30_E_EVD_2011 01 19 doc...

Страница 2: ...here are no obligations to update the manual continually The module is manufactured in accordance with applicable DIN and VDE standards such as VDE 0106 part 100 and VDE 0100 part 410 The CE marking o...

Страница 3: ...overheating 9 5 3 6 Signals 9 5 4 Output and threshold adjustment 10 5 4 1 Adjustable parameters at the adjustment mode 10 6 EXTERNAL FUNCTIONS 11 6 1 Output voltage sensor leads 11 6 2 Temperature c...

Страница 4: ...3 It is a ready for con nection unit for integration in a 19 sub rack according to DIN 41494 All operation and indication elements as well as the plugs are located at the front plate of the unit 2 Typ...

Страница 5: ...cted at the output If the SMPS output in the dead state is connected hard to a battery or other parallel operating SMPS then it results in a considerable surge of charging current which could lead in...

Страница 6: ...DC DC Converter PSC30 User Manual Page 6 24 2009 ELTEK VALERE DEUTSCHLAND GmbH UM_PSC30_E_EVD_2011 01 19 doc 5 Functions 5 1 Circuit diagram Fig 1 Circuit diagram PSC30...

Страница 7: ...r to the potential separation and voltage adaptation at the secondary side 5 Rectifier with fast switching diodes 6 LC filter for smoothing the DC voltage ripple at the rectifier output 7 Output filte...

Страница 8: ...eristic curve factory set a load distribution of about 10 and due to the optional active current distribution see section 7 3 factory adjustment necessary about 5 is attained During the adjustment of...

Страница 9: ...higher than adjusted level V This signal is included in collective failure signal It has its own relay contact on signaling connector too If the voltage value is okay Pin 13 and Pin 17 of X2 or Pin 1...

Страница 10: ...ustment value if you hold the key the value changes quicker press both keys UP DOWN together for a short time the SMPS changes back to adjust ment mode at this moment the changed value will be storage...

Страница 11: ...with connection of the shield to modules ground 6 3 External switch ON OFF The SMPS can be switched on off by an external signal The input is potential free due to an opto coupler and fulfills the req...

Страница 12: ...elements 24 48 60 110 V version Digital display for output voltage and current indication of the parameters and related values in the adjustment mode LED indicators Adjustment keys UP and DOWN Input s...

Страница 13: ...w operation elements 220 V version Digital display for output voltage and current indication of the parameters and related values in the adjustment mode LED indications Adjustment keys UP and DOWN Inp...

Страница 14: ...SC30 Vin 110VDC Pin 4 must be connected to plus DC input according to the table above due to the higher input current The PE connection bolt M4 is available at the front plate of the module see pictur...

Страница 15: ...of each unit have to be inter connected 3 At active current sharing mode of paralleled units all pin 8 of each module have to be intercon nected The analog GND pin 10 has to be interconnected too ATTE...

Страница 16: ...ON 1 5mm2 Pin assignment of X4 for PSC30 220V with signalling relay without CAN Bus Pin Function 1 external switch ON OFF 4 2 external switch ON OFF 3 Opto coupler emitter 4 Opto coupler collector Mai...

Страница 17: ...be connected too ATTENTION If active current sharing mode is enabled the use of external decoupling diodes and fuses as well in minus on the output side are not allowed 4 External switch ON Off with...

Страница 18: ...oltage Is the DC input voltage present Is the DC input switch in on position Is the input plug correctly connected Is the polarity correct or short circuit at the output Paralleled units incorrect pol...

Страница 19: ...HF field acc EN61000 4 part 3 10V m 30Mhz 1GHz power wires Burst test acc EN61000 4 part 4 2kV Surge test acc EN61000 4 part 5 4kV unsymmetric 2kV symmetric signal wires Burst Test acc EN61000 4 part...

Страница 20: ...V K per cell adjustable with external sensor optional external sense links for output voltage signaling with optocouppler VO O K Mains O K and Iconst external switch ON OFF function Operation in paral...

Страница 21: ...9 ELTEK VALERE DEUTSCHLAND GmbH UM_PSC30_E_EVD_2011 01 19 doc DC connector X2 24 110V DC SUB Min D connector 21WA4 220V DC front terminals 8 x 4mm2 COMBICON DC output front terminals 15 x 1 5mm2 signa...

Страница 22: ...48 to 60 72 0 1 60 to 73 129 6 1 110 to 135 259 2 1 220 to 270 Output voltage VO3 in V DC discharge test Adjusted value 22 2 1 Adjusting range 20 4 bis 24 44 4 1 40 8 to 48 55 5 1 51 to 60 99 9 1 91...

Страница 23: ...DC DC Converter PSC30 User Manual Page 23 24 2009 ELTEK VALERE DEUTSCHLAND GmbH UM_PSC30_E_EVD_2011 01 19 doc 10 3 Dimensions front view 24 to 110V...

Страница 24: ...DC DC Converter PSC30 User Manual Page 24 24 2009 ELTEK VALERE DEUTSCHLAND GmbH UM_PSC30_E_EVD_2011 01 19 doc 10 4 Dimensions front view 220V...

Отзывы: