![Eltek Valere PSC30 Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/eltek-valere/psc30/psc30_user-manual_2397271020.webp)
DC/DC Converter
PSC30
User Manual
Page 20 (24)
©2009. ELTEK VALERE DEUTSCHLAND GmbH.
UM_PSC30_E_EVD_2011-01-19.doc
digital instruments
for current:
displays values from 00.1 to 99.9 A DC
for voltage:
displays values from 00.1 to 999 V DC
External functions
signal
V<
relay
contact
(max. contact load:
24V DC/1A; 120V AC/0.5A)
collective
failure
relay
contact
(approx. 10 sec. delayed)
(max. contact load:
24V DC/1A; 120V AC/0.5A)
control wire
for active current sharing
discharge test mode /
boost charge mode
(voltage values adjustable)
temperature controlled
compensation of charge voltage
coefficient of temperature
-4mV/K per cell (adjustable)
with external sensor (optional)
external sense links
for output voltage
signaling with optocouppler „V
O
O.K.“ , „Mains O.K.“ and „I
const
“
external switch
ON/OFF function
Operation in paralleling
up to 10 modules possible, load sharing approx.10%
Construction
19"-cassette
for
mounting in 19“ subracks acc. to DIN 41 494
Protection
(mech.)
IP
20
Cooling
temperature-controlled
fan
cooling
Ambient temperature
0°C to 45°C,
0°C to 40°C at mounting in cabinet
Storage temperature
-30°C to + 70°C
Ambient conditions
IEC 721 part 3-3 class 3K3 / 3Z1 / 3B1 / 3C2 / 3S2 / 3M2
Max. operation altitude
1500 m
Mechanical construction
acc. to VDE 0160 rev. 5.88 section 7.2.2
Painting
color RAL 7035 (front panel only)
Dimensions
262 x 142 x 405 mm H x W x D (1/3-19“ x 6HU)
Connectors
Mains connector X1
3-pole, type GDM 2011