Maintenance can be carried out by the user as indicated at page 11.
Service must be perfmormed only by technically qualified personnel in accordance with
local rules and regulations. Make sure that the mains supply to the unit is disconnected
(page 12). Cleaning of the heat exchanger can be performed from outside as well.
MAINTENANCE AND SERVICE
Integral jumper set in position A (Fig. 20A) means “extract” mode.
Intergal jumper set in position B (Fig. 20B) means “intake” mode.
The jumper position defines both the air-flow direction when the unit is activated for the
first time (for the synchronisation) and the air-flow direction of the free-cooling mode.
JUMPER POSITION
If two or more units are controlled by means of the same controller (149-SEN-CTRLS or
similar), they always operate in a synchronised way. Wiring diagram as per Fig. 18.
SYNCHRONISATION IN CASE OF INSTALLATION WITH CONTROLLER
DIMENSIONS
270÷510
164
q
164
q
10
8
O
mm
A
270÷510
164
q
164
q
10
8
O
mm
270÷510
164
q
164
q
10
8
O
mm
C
D
ØE
External grille
270÷510
164
q
164
q
10
8
O
mm
B
Mori HR 100
Mori HR 150
A
164
218
B
46
51
C
164
218
D
270÷510
300÷560
Ø E
108
158
OPTION 2:
If two or more units are
not
connected under the same main switch, to reset
the synchronisation, press at the same time the black pin of each unit (Fig. 32-33) at
least 3 seconds.
Year 1
Inspection of filter cleanliness, if required wash under a tap (page 11)
Year 2
Inspection of filter cleanliness, if required wash under a tap (page 11)
Inspection of heat exchanger core, if required wash under a tap (page 12)
Year 3
Inspection of filter cleanliness, if required wash under a tap (page 11)
Year 4
Inspection of filter cleanliness, if required wash under a tap (page 11)
Inspection of heat exchanger core, if required wash under a tap (page 12)
Year 5
Inspection of filter cleanliness, if required wash under a tap (page11)