Volume Conversion Device EK260
Elster GmbH
63
MdMI3 Mode for monitoring I3
SC.I3
Source for monitoring I3
L1.I3
Limit 1 I3
SpI3
Status pointer for monitoring I3
By setting these values the following functions can be realised for Input 3 (Input 3
is only used as status input).
(For further details on entering a source for
SC.I3
: See Chap.2.3.2.
- Input 3 is an active warning input (input for warning signal):
Value
Setting
Comment
MdMI3
2
Monitoring mode: "Signal when SC.I3
≥
L1.I3"
SC.I3
03:228_0
= "St.I3"
Status on Input 3
L1.I3
1
Comparative value
SpI3
0.05_02:1.1
= I3 Warn.sig.
↑
Pointer to message "8" in status 3
- Input 3 is an inactive warning input (e.g. tamper detection):
Value
Setting
Comment
MdMI3
3
Monitoring mode: "Signal when SC.I3 < L1.I3"
SC.I3
03:228_0
= "St.I3"
Status on Input 3
L1.I3
1
Comparative value
SpI3
0.05_02:1.1
= I3 Warn.sig.
↑
Pointer to message "8" in status 3
- Input 3 is an active reporting input (input for report signal):
Value
Setting
Comment
MdMI3
2
Monitoring mode: "Signal when SC.I3
≥
L1.I3"
SC.I3
03:228_0
= "St.I3"
Status on Input 3
L1.I3
1
Comparative value
SpI3
0.05_02:1.1
= I3 Rep.sig.
↑
Pointer to message "13" in status 3 (report)
This setting is also established by loading a special parameter file for the
connection of an FE230 Function Expansion.
- Input 3 is an inactive reporting input (input for r eport signal):
Value
Setting
Comment
MdMI3
3
Monitoring mode: "Signal when SC.I3 < L1.I3"
SC.I3
03:228_0
= "St.I3"
Status on Input 3
L1.I3
1
Comparative value
SpI3
0.05_02:1.1
= I3 Rep.sig.
↑
Pointer to message "13" in status 3 (report)
Содержание 83 462 140
Страница 117: ...Volume Conversion Device EK260 Elster GmbH 117 A 2 Approval for Ex Zone 1 ...
Страница 118: ...Volume Conversion Device EK260 118 Elster GmbH ...
Страница 119: ...Volume Conversion Device EK260 Elster GmbH 119 ...
Страница 120: ...Volume Conversion Device EK260 120 Elster GmbH ...
Страница 121: ...Volume Conversion Device EK260 Elster GmbH 121 ...