924EHUCE4.00 - Mistral
Humidifier
13.7 MISTRAL MODBUS ADDRESSES
13.7.1 Table of Modbus addresses
Par. Description
Val.
Adr.
R/W
DATA
SIZE
CPL
MU
Range
SETPOINT group
SP Humidity setpoint.
1539 R/W WORD
---
%
r1...r2
CONFIGURATIONS Group
CFG Operating mode.
1540 R/W BYTES
---
---
0...10
ANALOGUE INPUTS group
P1 Water conductivity.
1541 R/W WORD
---
μS*cm
70...1250
MAIN REGULATOR group
r0 Hysteresis. With CFG
=2,3,4,7,8,9.
1545 R/W WORD
---
%
2...20
r1 Minimum humidity setpoint value. With CFG
=2,3,4,7,8,9.
1546 R/W WORD
---
%
0...r2
r2 Maximum humidity setpoint value. With CFG
=2,3,4,7,8,9.
1547 R/W WORD
---
%
r1...100
r3
Minimum delay time between two consecutive humidity production
activations.
With CFG
≠
10.
1548 R/W WORD
---
s
1...240
r4 Proportional band. With CFG
=2,3,4,7,8,9.
1549 R/W WORD
---
%
0...50
r5 Minimum humidity production. With CFG
≠
10.
1550 R/W WORD
---
%
0....r6
r6 Maximum humidity production. With CFG
≠
10.
1551 R/W WORD
---
%
r5...100
REGULATOR PROTECTION group
c0 Number of continuous idle hours causing the water reservoir to empty.
1556 R/W WORD
---
h
0...250
c1 Number of operating hours causing the water reservoir to empty.
1557 R/W WORD
---
h
0...250
FANS group
F0
Fanspeed.
1559 R/W 3 BIT
---
---
0...3
F4
Fanoffdelayfromswitchingmist-makeroff(
with CFG = 10).
1563 R/W WORD
---
s
0...240
F5
Fanoperationtimeafteremptyingduetoinactivity.
1564 R/W WORD
---
s
0...999
TEMPERATURE ALERTS group
A5 Low humidity alert threshold only if CFG
=2,3,4,7,8,9.
1568 R/W WORD
---
---
0...100
A6 High humidity alert threshold only if CFG
=2,3,4,7,8,9.
1569 R/W WORD
---
---
0...100
A7 High low humidity alert delay only if CFG
=2,3,4,7,8,9
.
1570 R/W WORD
---
s
0...999
A13 Number of fan operating hours to signal partial operating hours.
1574 R/W WORD
--- 1000h
0...99
DIGITAL INPUTS group
i0 ID2 port digital input polarity.
1607 R/W 1 BIT
---
---
0/1
PASSWORD group
PAS Parameter access password.
1609 R/W WORD
Y
num -99...999
EVLINK DATALOGGING group
bLE Serial port configuration for EVconnect/EPoCA connectivity.
1612 R/W WORD
---
---
0...99
rE0 Datalogger sampling interval.
1613 R/W WORD
---
min
0...240
rE1 Enable data logging for datalogger.
1614 R/W 1 BIT
---
---
0/1
MODBUS SERIAL CONFIGURATION group
LA1 COM1 serial line modbus protocol controller address.
1615 R/W WORD
---
num
1...247
LA1 COM2 serial line modbus protocol controller address.
1616 R/W WORD
---
num
1...247