Parameter setting
Sensor Vari KNX 3L-TH-D
• Status: 19.10.2016 • Errors excepted. Subject to technical changes.
Activate the summer compensation.
Using the points 1 and 2, define the outdoor temperature range in which the target
value for the indoor temperature is to be adapted linearly. Then, specify which indoor
temperature target values are to be valid below point1 and above point 2.
Standard values according to DIN EN 60529
Point 1: External temperature = 20°, Target value = 20°C.
Point 2: External temperature = 32°, Target value = 26°C.
Set the send pattern for the summer compensation.
If necessary, activate the block for the summer compensation and set what a 1 or 0 at
the block input means and what happens in the event of a block.
Use summer compensation
No •
Yes
Characteristic curve description:
External temperature point 1 (in 0.1°C
increments)
0 ... 500 ; 200
Outdoor temperature point 2 (in 0.1°C
increments)
0 ... 500 ; 320
below point 1
the target value is (in 0.1°C)
0 ... 500 ; 200
above point 2
the target value is (in 0.1°C)
0 ... 500 ; 260
Send pattern
• periodically
• on change
• on change and periodically
on change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • 1°C • 2°C • 5°C
Send cycle
(if sent periodically)
5 s ... 2 h; 1 min
Use block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first call
0 • 1
Action when locking
• do not send
• Send value
Value (in increments of 0.1°C)
(if a value is sent during blocking)
0 ... 500; 200