40
Parameter setting
Sensor Vari KNX 3L-TH-D
• Status: 19.10.2016 • Errors excepted. Subject to technical changes.
With both of the methods for specifying the threshold values the hysteresis is set.
Switching output
Define which value the output transmits if the threshold value is exceeded or undercut.
Set the delay for the switching and in which cases the switch output transmits.
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry
means and what happens in the event of a block.
Object value limit (min.) in Lux
1000 … 150000
Object value limit (max.) in Lux
1000 … 150000
Type of threshold change
Absolute value • Increase/decrease
Increment in Lux
(upon increase/decrease change)
1000 • 2000 • 5000 • 10000 • 20000
Hysteresis setting
in % • absolute
Hysteresis in % of the threshold value
(for setting in %)
0 … 100; 50
Hysteresis in Lux
(for absolute setting)
0 … 150000; 30000
When the following conditions apply, the
output is
(LV = Threshold value)
• GW above = 1 | GW - Hyst. below = 0
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1
Delays can be set via objects
(in seconds)
No • Yes
Delay from 0 to 1
none • 1 s … 2 h
Delay from 1 to 0
none • 1 s … 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(if sent periodically)
5 s ... 2 h
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first call
0 • 1
Action when locking
• Do not send message
• send 0
• send 1