Parameter setting
Sensors Mini-Sewi KNX TH-L-Pr and Mini-Sewi KNX L-Pr
• Version: 30.08.2018 • Technical changes and errors excepted.
If setpoint values are entered separately:
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
If the comfort setpoint is used as the basis without a switching object, a dead zone is
specified for the control mode "heating
and
cooling" to avoid direct switching from he-
ating to cooling.
Standby setpoint
Standby mode is usually used for daytime mode when people are absent.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
Eco setpoint
Eco mode is usually used for night mode.
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
Max. object value heating/cooling
(in 0.1 °C)
-300…800; 280
Minimum base setpoint (in 0.1°C)
-300…800; 160
Maximum base setpoint (in 0.1°C)
-300…800; 280
Reduction by up to (in 0.1°C)
0…100; 50
Increase by up to (in 0.1°C)
0…100; 50
Dead zone between heating and cooling
(only if both heating AND cooling are used)
1…100; 50
Starting heating/cooling setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 180
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
Max. object value heating/cooling
(in 0.1 °C)
-300…800; 280
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 30
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 30