background image

 

30309578   

         

                                                                                             

                     

  Issue 1.06

 

                                       

 

 

Features 

  Address can be set in field. 

  Fault self-diagnostic.   

  Rate  of  rise  and  fixed  temperature,  and  fixed  temperature 

programmable 

  Reed switch testing. 

  Output terminal for remote indicator available. 

  Complying with UL 521. 

  Polling LED can be set to OFF. 

Description 

DI-M9103  Intelligent  Rate  of  Rise  and  Fixed  Temperature  Heat 
Detector  (the  detector)  is  a  new  addressable  fire  alarm  device 
cooperating with GST intelligent fire alarm control panels (FACP) to 
build  a  fire  detection  system.  The  detector  shows  fire  condition  by 
LED indicator and transmits alarm signals to the FACP.     

Connection and Wiring 

The detector bottom is shown in Fig. 1 and the base in Fig. 2. 

5

45

75

Cable Entry

Mounting
Hole

 

Fig. 1                              Fig. 2 

Please install the base according to following steps: 

1) 

Locate  mounting  holes  on  the  rubber  layer  of  the  base 
according to the holes on the back box, and punch the holes 
with a screwdriver. 

2) 

Count  the  number  of  cables  needed  and  punch  correct 
quantity  of  holes  with  a  screwdriver  on  the  rubber  layer. 
Thread the cables through the cable entry holes.   

3) 

Install the base onto the back box with screws. 

Warning: Do not punch mounting holes and cable entry holes 
bigger than needed. Do not punch more holes than needed. 

There are four terminals with numbers on the base.   

1&3: Loop connection (polarity-insensitive) 

2: Positive terminal of remote indicator 

4: Negative terminal of remote indicator 

The system connection is shown in Fig. 3.   

Remote Indicator

-

+

LOOP OUT

Addressable Detector

Remote Indicator

Addressable Detector

+

-

LOOP IN

 

Fig. 3 

Recommended Wiring 

1.0mm

or above fire cable for all terminals laid through metal conduit 

or flame retardant conduit, subject to local codes.   

Note

It

’s  recommended  to  use  cables  of  different  colors  to 

avoid incorrect wiring. 

 

 

Installation 

Refer to 

D Series Detector Application Bulletin 

for additional 

installation instructions. 
First fix the orientation base with two tapping screws. Then  align A 
(Fig. 1) on the bottom of the detector to B (Fig. 2) of the base, and 
rotate the detector clockwise to mark C. 
Mounting of the detector is shown in Fig. 3. 

Detector

Base

Conduit

Electric Box

53.3mm

Fig. 3

 

Application 

The  detector  is  especially  applicable  to  places  where  fire  occurs 
with sharp rise of temperature. Used together with smoke detectors, 
it can detect fire with more reliability to reduce losses. 

The  detector  can  be  addressed  in  field  by  using  P-9910B 
programmer.  Please  refer  to 

P-9910B  Hand  Held  Programmer 

Installation and Operation Manual 

for details. 

The default class of the detector is rate of rise and fixed temperature 
(7) and polling LED is normal. The parameter can be modified using 
GST handheld programmer. 

When the programmer is in standby state, entering unlock password 
and pressing “Clear”, it will be unlocked. Pressing 

Function

 followed 

by 

4

,  there  will  be  a  “-”at  the  last  digit.  Entering  different  number 

corresponding  to  the  classes 

(“7”  for  rate  of  rise  and  fixed 

temperature, 

“8” for fixed temperature) followed by “Program”, there 

will be a 

“P” shown on the screen, indicating its class is programmed. 

Pressing 

“Clear”  can  clear  the  “P”,  and  entering  locking  password 

followed by 

“Clear” will exit. 

Table 1 Detector setting parameters 

Input 

Number 

Class 

Polling 

LED 

State 

Rate of rise and fixed 

temperature 

Normal 

Fixed temperature   

Normal 

135 

Rate of rise and fixed 

temperature 

OFF 

136 

Fixed temperature   

OFF 

 

Read  Heat  Detector  Class: 

When  the  programmer  is  in  standby 

state,  pressing 

Test”,  it  will  display  address  of  the  detector. 

Pressing 

“Up”

,  it  will  display  sensitivity  level,  device  type  and  heat 

detector class in turn.   

DI-M9103 Intelligent Rate of Rise 

and Fixed temperature Heat Detector 

Reviews: