9
Transfer protocol
Radio actuator KNX RF MSG-DST
Version: 27.06.2018 • Technical changes and errors excepted.
3.
Transfer protocol
3.1. List of all communication objects
Abbreviations:
R
Read
W Write
C
Communication
T
Transfer
No.
Name
Func-
tion
Flags
Data Point
Type
Size
1
Software version
Readable
R-C-
[217.1]
DPT_Version
2 Bytes
100
Status automatic or manual
mode
Output
R-CT
[1.1]
DPT_Switch
1 Bit
101
Manual long-term
Input
RWC-
[1.8]
DPT_UpDown
1 Bit
102
Manual short-term
Input
RWC-
[1.10]
DPT_Start
1 Bit
103
Manual movement position
Input
RWC-
[5.1]
DPT_Scaling
1 Byte
104
Manual slat position
Input
RWC-
[5.1]
DPT_Scaling
1 Byte
105
Automatic mode long-term
Input
RWC-
[1.8]
DPT_UpDown
1 Bit
106
Automatic mode short-term
Input
RWC-
[1.10]
DPT_Start
1 Bit
107
Automatic mode movement
position
Input
RWC-
[5.1]
DPT_Scaling
1 Byte
108
Automatic mode slat position
Input
RWC-
[5.1]
DPT_Scaling
1 Byte
109
Change from manual to
automatic mode
Input
RWC-
[1.1]
DPT_Switch
1 Bit
110
Automatic mode blocking object
Input
RWC-
[1.1]
DPT_Switch
1 Bit
111
current movement position
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
112
current slat position
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
113
Status object
Output
R-CT
[1.1]
DPT_Switch
1 Bit
114
Approach position memory for
manual
Input
RWC-
[1.1]
DPT_Switch
1 Bit
Содержание KNX RF-MSG-DST