6
Installation and start-up
Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH
• Version: 11.06.2018 • Technical changes and errors excepted.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2. Installation location
Install and use only in dry interior rooms!
Avoid condensation.
The
Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH
are installed in a false ceil-
ing or on wall or ceiling in a standard connection socket (Ø 60 mm, 42 mm deep).
When selecting an installation location, please ensure that the measurement results of
temperature or humidity
are affected as little as possible by external influences.
Possible sources of interference include:
•
Direct sunlight
•
Drafts from windows and doors
•
Draughts from ducts coming from other rooms or the outdoors
•
Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
•
Connection lines and empty ducts which lead from warmer or colder areas to
the sensor
Measurement variations from such sources of interference must be corrected in the
ETS in order to ensure the specified accuracy of the sensor (offset).
2.3. Installation of the sensor
2.3.1. Installation in false ceiling
Connect the bus line to the KNX terminal (red/black).
Place the device in the installation opening in the ceiling. For this, fold the clamps up-
wards and guide the device through the installation opening with the clamps first.
Intra-Sewi KNX T(H)
is automatically fixed by the clamps.