background image

22

Parameter setting

Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH

 • Version: 11.06.2018 • Technical changes and errors excepted.

Select the 

mode to be activated after reset

 (e.g. power failure, reset of the line via

the bus) (Default). 
Then configure a temperature control 

block

 via the blocking object.

Specify when the current 

control variables

 of the controller are to be 

sent

 to the bus.

Periodic sending is safer, in case a message does not reach a recipient. You may also
set up periodical monitoring by the actuator with this setting. 

The 

status object

 reports the current status of the control variables (0% = OFF, 

>0% = ON) and may for example be used for visualisation, or to switch off the 
heating pump as soon as the heating is switched off.

Then define the 

type of control

. Heating and/or cooling may be controlled in two le-

vels.

Switch mode via

• two 8 Bit objects (HVAC Modes)
• three 1 bit objects

Mode after reset

• Comfort
• Standby
• Eco
• Building protection

Behaviour of the blocking object with value

• 1 = Block | 0 = release
• 0 = block | 1 = release

Value of the blocking object after reset

0 • 1

Send control variable

• on change 
• on change and periodically

  from change (in % absolute)

1...10; 2

  Cycle
 

 (if sent periodically)

5 s • ... • 5 min • … • 2 h

Send status objects

• on change 
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically

  Cycle
  

(if sent periodically)

5 s • ... • 5 min • … • 2 h

Type of control

• Single level heating
• Dual-level heating
• Single-level cooling
• Dual-level cooling
• Single-level h single-level cooling
• Dual-level h single-level cooling
• Dual-level h dual-level cooling

Содержание Intra-Sewi KNX T

Страница 1: ...Intra Sewi KNX T Intra Sewi KNX TH Ambient Climate Sensors Item numbers Intra Sewi KNX T 70660 white 70665 black Intra Sewi KNX TH 70661 white 70666 black EN Installation and Adjustment...

Страница 2: ......

Страница 3: ...Transfer protocol 11 4 1 List of all communication objects 11 5 Parameter setting 19 5 1 Behaviour on power failure restoration of power 19 5 2 General settings 20 5 3 Temperature Measurement 20 5 4...

Страница 4: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Страница 5: ...asurement value and external value can be set as a percentage Threshold values can be adjusted per parameter or via communication objects PI controller for heating one or two stage and cooling one or...

Страница 6: ...ht above wall approx 5 mm height in wall installation approx 31 mm incl clamps Total weight approx 50 g Ambient temperature Operation 20 60 C storage 20 70 C Ambient humidity max 95 RH avoid condensat...

Страница 7: ...e are unprotected live components inside the device National legal regulations are to be followed Ensure that all lines to be assembled are free of voltage and take precautions against accidental swit...

Страница 8: ...rnal influences Possible sources of interference include Direct sunlight Drafts from windows and doors Draughts from ducts coming from other rooms or the outdoors Warming or cooling of the building st...

Страница 9: ...entation as shown in the chapter Coverage area of the motion detector Connect the bus line to the KNX terminal red black Clamp the device in the support ring so that the springs on the device snap ove...

Страница 10: ...ck view connection The connection is made with the KNX terminal red black to KNX TP Fig 3 Connector socket with 60 mm 42 mm deep 1 Support ring screwed to the socket 2 Springs hold the device firmly o...

Страница 11: ...ater e g rain or dust This can damage the electronics You must not exceed a relative humidity of 95 Avoid condensation The airing lamella must not be closed or covered The device must not be painted o...

Страница 12: ...10 Maintenance Sensors Intra Sewi KNX T and Intra Sewi KNX TH Version 11 06 2018 Technical changes and errors excepted...

Страница 13: ...Bytes 58 Temperature sensor measured value Output R CT 9 1 DPT_Value_Temp 2 Bytes 59 Temperature sensor measured value total Output R CT 9 1 DPT_Value_Temp 2 Bytes 60 Temperature sensor measured value...

Страница 14: ...1 0 Input WC 1 1 DPT_Switch 1 Bit 80 Temp thresholdV 3 Switching delay from 0 to 1 Input WC 7 5 DPT_TimePeriodSec 2 Bytes 81 Temp thresholdV 3 Switching delay from 1 to 0 Input WC 7 5 DPT_TimePeriodS...

Страница 15: ...eating Input Output WCT 9 1 DPT_Value_Temp 2 Bytes 107 Temp control Setpoint Standby heat 1 0 Input WC 1 1 DPT_Switch 1 Bit 108 Temp control Setpoint Standby cooling Input Output WCT 9 1 DPT_Value_Tem...

Страница 16: ...ue_Humidity 2 Bytes 133 Humidity sensor measured value total Output R CT 9 7 DPT_Value_Humidity 2 Bytes 134 Humidity sensor measured value min max query Input WC 1 17 DPT_Trigger 1 Bit 135 Humidity se...

Страница 17: ...oldV 3 Swit ching output Output R CT 1 1 DPT_Switch 1 Bit 155 Humidity thresholdV 3 Swit ching output block Input WC 1 1 DPT_Switch 1 Bit 156 Humidity thresholdV 4 Abso lute value Input Output WCT 9 7...

Страница 18: ...0 Cooling medium temp Swit ching delay from 0 to 1 Input WC 7 5 DPT_TimePeriodSec 2 Bytes 181 Cooling medium temp Swit ching delay from 1 to 0 Input WC 7 5 DPT_TimePeriodSec 2 Bytes 182 Cooling medium...

Страница 19: ...Scaling 1 Byte 200 Actuating variable comparator 2 Input 5 Input WC 5 1 DPT_Scaling 1 Byte 201 Actuating variable comparator 2 Output Output R CT 5 1 DPT_Scaling 1 Byte 202 Actuating variable comparat...

Страница 20: ...Ucount 1 Bit 2x1 Byte 226 AND logic 2 8 bit output B Output R CT 5 010 DPT_ Value_1_Ucount 1 Bit 2x1 Byte 227 AND logic 2 Block Input WC 1 1 DPT_Switch 1 Bit 228 AND logic 3 1 bit switching out put Ou...

Страница 21: ...put Output R CT 1 2 DPT_Bool 1 Bit 241 OR logic 2 8 bit output A Output R CT 5 010 DPT_ Value_1_Ucount 1 Bit 2x1 Byte 242 OR logic 2 8 bit output B Output R CT 5 010 DPT_ Value_1_Ucount 1 Bit 2x1 Byt...

Страница 22: ...d sent to the bus Use the Reset temperature min max value objects to reset the values to the current readings The values are not retained after a reset Send delay after reset bus restoration for Measu...

Страница 23: ...for the temperature control include the setpoint temperatures for the in dividual modes Objects are used to determine which mode is to be selected A change of mode may be triggered manually or automat...

Страница 24: ...e heating is switched off Then define the type of control Heating and or cooling may be controlled in two le vels Switch mode via two 8 Bit objects HVAC Modes three 1 bit objects Mode after reset Comf...

Страница 25: ...extension This allows the user to maintain the comfort setpoint value for a longer time e g when having guests The duration of this comfort extensi on period is set After the comfort extension period...

Страница 26: ...n which the setpoint value may be changed If the comfort setpoint value is used as a basis If the comfort setpoint value is used as a basis the reduction increment of the value is set Eco setpoint Eco...

Страница 27: ...t protection mode General control variables This setting appears for the control types Heating and Cooling only Here you can decide whether to use a common control variable for heating and cooling If...

Страница 28: ...g via objects is ignored Set the threshold value directly in the application program using parameters or define them via the bus using a communication object Threshold value setting via parameter Set...

Страница 29: ...Start threshold value in 0 1 C valid until first communication 300 800 200 Object value limit min in 0 1 C 300 800 Object value limit max in 0 1 C 300 800 Type of threshold value change Absolute value...

Страница 30: ...ase of 2 level heating heating is controlled via a PI or a 2 point control Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At val...

Страница 31: ...ing system at this point observe ma nufacturer s instructions Now specify what should be sent when the control is blocked Set a value greater 0 OFF to receive a basic heating level e g for floor heati...

Страница 32: ...reshold range If separate control variables are used select whether the control variable of the 2nd le vel is a 1 bit object on off or an 8 bit object on with percentage off Application Warm water hea...

Страница 33: ...viation from the setpoint value which reaches maximum variable value i e the point at which maximum cooling power is activated The reset time shows how quickly the controller responds to deviations fr...

Страница 34: ...ts frequent on off switching of temperatures in the th reshold range If separate control variables are used select whether the control variable of the 2nd le vel is a 1 bit object on off or an 8 bit o...

Страница 35: ...calculation if desired If an external portion is used all of the following settings threshold values etc are related to the overall reading The minimum and maximum readings can be saved and sent to th...

Страница 36: ...alue setting using parameter Set the threshold values and hysteresis directly Threshold value setting using a communication object Define how the threshold value is to be received from the bus Basical...

Страница 37: ...000 Type of threshold value change Absolute value Increase decrease Increment upon increase decrease change 0 1 RH 2 0 RH 20 0 RH Hysteresis setting in absolute Hysteresis in 0 1 RH 0 1000 100 Hystere...

Страница 38: ...of the blocking object At value 1 block At value 0 release At value 0 block At value 1 release Blocking object value before first communi cation 0 1 Behaviour of the switching output On block Do not s...

Страница 39: ...is valid until the first communication of a new setpoint value For units which have already been ta ken into service the last communicated setpoint value can be used Basically an air humidity range i...

Страница 40: ...value difference between the two levels must be defined i e the setpoint value which when exceeded triggers the switch to the 2nd level Determine the deviation from the setpoint value at which the ma...

Страница 41: ...ring of the coolant temperature if required The menus for setting the monitoring are displayed 5 9 1 Cooling medium temp monitoring A threshold value can be set for the temperature of the coolant whic...

Страница 42: ...used A set offset will be retained until a new value or a change is transferred The current value is saved so that it is retained in the event of a power supply failure and will be available once the...

Страница 43: ...communication None 1 s 2 s 5 s 10 s 2 h Switching delay from 1 to 0 for setting via objects valid until 1st communication None 1 s 2 s 5 s 10 s 2 h Switching output sends on change on change to 1 on c...

Страница 44: ...e bus if the limits of the comfort field are exceeded In this way it is for example possible to monitor compliance with DIN 1946 standard values or even to define your own comfort field Switching outp...

Страница 45: ...rol variable comparator should output and activate the input objects to be used Transmission patterns and blocks can also be set Sending pattern not on change on change to comfortable on change to unc...

Страница 46: ...bject and periodically Send cycle if sent periodically 5 s 10 s 30 s 5 min 2 h At and above change of if sent on change 1 2 5 10 20 25 50 Analysis of the blocking object at value 1 block at value 0 re...

Страница 47: ...ions OR logic not active active OR logic 4 not active active 1 2 3 4 Input do not use Logic inputs 1 16 Logic inputs 1 16 inverted all switching events that the device provides see Connection inputs o...

Страница 48: ...255 100 360 63 0 Output value object B if monitoring period is exceeded 0 255 100 360 63 0 Send pattern on change of logic on change of logic to 1 on change of logic to 0 on change of logic and period...

Страница 49: ...t 9 Logic input 9 inverted Logic input 10 Logic input 10 inverted Logic input 11 Logic input 11 inverted Logic input 12 Logic input 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Lo...

Страница 50: ...Cooling 2 temperature controller active Cooling 2 temperature controller inactive Only for model Mini Sewi KNX TH Humidity sensor malfunction ON Humidity sensor malfunction OFF Switching output 1 Hum...

Страница 51: ...changes and errors excepted Switching output AND logic 1 Switching output AND logic 1 inverted Switching output AND logic 2 Switching output AND logic 2 inverted Switching output AND logic 3 Switchin...

Страница 52: ...bH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de Technical support 49...

Отзывы: