11
Transfer protocol
Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH
• Version: 11.06.2018 • Technical changes and errors excepted.
4.
Transfer protocol
Units:
Temperatures in degrees Celsius
Air humidity in %
Absolute air humidity in g/kg and/or g/m
3
Variables in %
4.1.
List of all communication objects
Abbreviation flags:
C
Communication
R
Read
W Write
T
Transfer
U
Update
No. Text
Function Flags Data Point Type
Size
0
Software version
Output
R-CT
[217.1]
DPT_Version
2 Bytes
56
Temperature sensor: malfunc-
tion
Output
R-CT
[1.1]
DPT_Switch
1 Bit
57
Temperature sensor: measured
value external
Input
-WCT [9.1]
DPT_Value_Temp
2 Bytes
58
Temperature sensor: measured
value
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
59
Temperature sensor: measured
value total
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
60
Temperature sensor: measured
value min./max. query
Input
-WC- [1.17]
DPT_Trigger
1 Bit
61
Temperature sensor: measured
value minimum
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
62
Temperature sensor: measured
value maximum
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
63
Temperature sensor: measured
value min./max. reset
Input
-WC- [1.17]
DPT_Trigger
1 Bit
66
Temp. thresholdV 1: Absolute
value
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
67
Temp. thresholdV 1: (1:+ | 0:-)
Input
-WC- [1.1]
DPT_Switch
1 Bit
68
Temp. thresholdV 1: Switching
delay from 0 to 1
Input
-WC- [7.5]
DPT_TimePeriodSec
2 Bytes
69
Temp. thresholdV 1: Switching
delay from 1 to 0
Input
-WC- [7.5]
DPT_TimePeriodSec
2 Bytes
Содержание Intra-Sewi KNX T
Страница 2: ......