16
Transfer protocol
Nunio KNX M-T push button
• Version: 25.02.2021 • Technical changes and errors excepted.
8.
Transfer protocol
Units:
Temperatures in degrees Celsius
8.1. List of all communications objects
Abbreviation flags:
C
Communication
R
Read
W Write
T
Transmit
U
Update
No
Text
Function
Flags
DPT type
Size
0
Software version
Output
R-CT
[217.1] DPT_Ver-
sion
2 Bytes
31
Area operation
on/off
Input
-WC-
[1.1] DPT_Switch 1 Bit
32
Area operation Output: Switch
Output
R-CT
depending on
setting
2 Bytes
33
Display basic brightness
Input /
Output
-WC-
[5.1] DPT_Scal-
ing
1 Byte
34
Display operating brightness
Input /
Output
-WC-
[5.1] DPT_Scal-
ing
1 Byte
35
Display automatic switching-off
Input
-WC-
[1.3] DPT_Enable 1 Bit
47
Temperature sensor: malfunction
Output
R-CT
[1.1] DPT_Switch 1 Bit
48
Temperature sensor: measured
value external
Input
-WCT
[9.1] DPT_Val-
ue_Temp
2 Bytes
49
Temperature sensor: measured
value
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes
50
Temperature sensor: measured
value total
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes
51
Temperature sensor: measured
value min./max. query
Input
-WC-
[1.17] DPT_Trig-
ger
1 Bit
52
Temperature sensor: measured
value minimum
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes
53
Temperature sensor: measured
value maximum
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes
54
Temperature sensor: measured
value min./max. reset
Input
-WC-
[1.17] DPT_Trig-
ger
1 Bit
58
Menu change (1 = Temp.controller
menu| 0 = Sensor menu)
Input
-WC-
[1.1] DPT_Switch 1 Bit
61
Temp.control: HVAC mode (prior-
ity 1)
Input /
Output
RWCT depending on
setting
1 Byte