3
Description
Indoor sensor KNX TH-B-UP
• Software version 3.1 and higher
Version: 22.02.2017 • Technical changes and errors excepted.
Additionally
required (not included in the deliverables):
•
Junction box Ø 60 mm, 42 mm depth
•
Frame (for insert 55 x 55 mm), compatible with the switch scheme used in the
building
1.2. Technical specifications
* Please note the information on
The product is compliant with the provisions of EU guidelines.
Housing
Plastic (partially painted)
Colours
• White, glossy (similar to RAL 9016 Traffic White)
• Aluminium, matt
• Anthracite, matt
• Special colours on request
Assembly
Flush mounting, wall mounting in junction box Ø 60 mm,
42 mm depth
Protection category
IP 20
Dimensions
Housing approx. 55 x 55 (W x H, mm), installation depth
approx. 15 mm,
Baseplate approx. 71 x 71 (W x H, mm),
Total weight
approx. 50 g
Ambient temperature
Operation 0…+50°C, storage -10…+60°C
Ambient humidity
max. 95% RH, avoid condensation
Operating voltage
KNX bus voltage
Bus current
max. 6 mA, max 10 mA when programming LED active
Data output
KNX +/- bus plug-in terminals
BCU type
Integrated microcontroller
PEI type
0
Group addresses
max. 254
Assignments
max. 254
Communication objects
215
Temperature measuring
range
0…+50°C
Temperature resolution
0.1°C
Temperature accuracy*
±0.5°C at 0...+50°C
Humidity measuring range
0…100%
Humidity resolution
0.1%
Humidity accuracy
±7,5% RH at 0…10% RH
±4,5% RH at 10…90% RH
±7,5% RH at 90…100% RH
Humidity drift
± 0.5% RH per year in normal atmosphere