MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02
– 19 March 2015
23
6.3 EMC STANDARD / SAFETY STANDARD
Our product are manufactured according to the following EMC international grade standard and has passed the
CE authentication:
EMC STANDARD NUMBER
SAFETY STANDARD NUMBER
IEC62040-2
IEC62040
-
1
IEC61000-4-2
GB4943-5
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
6.4 PRODUCT PERFORMANCE
MODEL
MISSION 1000
MISSION 2000
MISSION 3000
RATED CAPACITY (VA/W)
1000VA / 800W
2000VA / 1600W
3000VA / 2400W
INP
UT
Input
Single phase and earthing
Voltage range
115±5VAC - 295±5VAC
Frequency range
45Hz-55Hz@50HZ/55Hz-65Hz@60HZ
Power factor
≥0.98
ECO range
Setting output voltage ±20VAC
Bypass range
186VAC - 252VAC
Current harmonic
≤7% (100% non linear load)
O
UT
P
UT
Output style
Single phase and earthing
Rated voltage
208/220/230/240VAC
Power factor
0.8
Voltage precision
±2%
Output
Frequency
Line mode
1.
When input frequency is in the range, the output frequency is the
same as that of input.
2.
When input frequency is out of the range, the output frequency is
(50/60±0.2)Hz when turn to battery mode.
Battery
mode
(50/60 ±0.2)Hz
Crest ratio
3:1
Transfer time
Mains ←→ battery = 0ms
Overload
capacity
Battery
mode
108%±5%<load≤150%±5% >30s cut off output and warn,
150%±5%<load<200%±5% >300ms cut off output and warn
Line mode
108%±5%<load≤150%±5% >30s transfer to bypass and warn
150%±5%<load<200%±5% >300ms transfer to bypass and warn
Efficiency
Line mode
Full load≥88%
Battery
mode
Full load≥85%
ECO
Full load≥94%
Output voltage distortion
≤3%(100% linear load)
≤5%(100% non linear load)