MISSION 1K●2K●3K
SINGLE PHASE
Rev. 02
– 19 March 2015
16
second (less than 2 seconds) the selection is confirmed. Now, the EPO function configuration is
completed and "" - P "or" + P "under" EPO "will remain fixed.
4
Exit the configuration interface. Press and hold the configuration function key
for more than 2
seconds to exit this configuration interface and return to the main interface.
4.3.10 Discharge Low voltage function setting (Eod)
1
To enter the configuration interface, press and hold the configuration function key
for more than 2
seconds, then access the Configuration Interface. Press the key
until you reach the Eod menu (10),
the word "Eod" flashes:
2
Start the Low Voltage selection mode interface: press and hold the configuration function key
for more than half second (less than 2 seconds), the EOD output interface is accessed, at this
point the written "Eod" will remain fixed. The numeric value below Eod will blink. Press the key
to
select the numeric value of the desired "Eod" function. Selectable voltages are 10.0V, 10.5V, 11V,
(default is 10.0V).
3
Confirm the Low Voltage selection mode interface. After selecting the numeric value, hold down the
function configuration key
for more than half a second (less than 2 seconds). Now, the "Eod"
mode configuration is completed and the numeric value under "Eod" will remain fixed.
4
Exit the configuration interface. Press and hold the button
for more than 2 seconds to exit this
configuration interface to return to the main interface.
4.3.11 Frequency converter function setting (OPF)
1
To enter the configuration interface, press and hold the configuration function key
for more than 2
seconds, then access the Configuration Interface. Press the key
until you reach the OPF menu
(11), the word "OPF" flashes:
2
Start frequency converter selection mode interface: press and hold the configuration function key
for more than half second (less than 2 seconds), access to the OPF converter configuration interface, at
this point the write "OPF" will remain fixed. The value of the output frequency under OPF will blink.
Press the key
to select from the available options. The selectable frequencies are 50Hz (output
frequency fixed at 50Hz and converter mode activated), 60Hz (output frequency fixed at 60Hz and
converter mode activated) and IPF (inverter mode inactive).
3
Confirm the frequency converter selection mode interface. After selecting the desired setting, hold down
the function configuration key
for more than half a second (less than 2 seconds). Now, the "OPF"
mode configuration is completed and the numeric value under "OPF" will remain fixed.