background image

Brief Description

•   Suitable as :

  Multistage Controller or

  Differential Controller with    

  limitation contacts

•   Operating Modes: 

  4-Stage Controller,  

 

  Double 2-Stage Controller, 

  3-Stage-Cont Alarm, 

  Differential Controller

•   Analog Output 0-10VDC for P/PI- 

  control or Remote Displays

•  

Alarm Limits / Alarm Relay

•   Different Sensor Types

•   Setpoint shift by Real Time Clock

•  

Minimum Idle Time

•  

RS-485-Interface

ELEKTRONISCHE  REGELUNGEN  GMBH

Can be used for

•  Cooling, Heating and HVAC   

  Applications

Operating Elements

Parameters 

(setpoints, times, etc.)

All selectable parameters hold a parameter number (e.g. P04), you will find a 

listing on the next page.

Calling up and editing

Press key 'P' ...................parameter number appears 

Use '

/

'  .......................select desired parameter (hold key for autoscroll)

Press "P" again ...............parameter value appears

Use keys '

/

' ................adjust parameter value (hold key for autoscroll)

Press 'P' again ................value is stored, back to parameter no.

Unlock Keys / Access code

To prevent un-authorized persons from editing parameter values, there is a 

locking function which allows only the most important parameters to be changed 

at any time. All other parameters must be unlocked as follows: 

-  enter access code before programming at parameter 

P41 

or

-   directly at the parameter to be changed. If a code no. is necessary the    

  display shows "C00". Set the matching code no. by the "

/

"-keys (70 or  

  88, see parameter listing) and confirm by "P".

If no key is hit for about four minutes, the access code is cancelled and the 

editing function is locked automatically. 

After entering of the code '70' the control functions will be disabled. 

They will be restartet if the code will be changed manually (e.g. to 88 

for other parameters) or will be resetted automatically after 4 minutes 

without any press on a button.

Start-up behavior

Directly after start-up the display shows "700" (controller type), after that a 

display test passes.

How to find out the controller type

-  Press key "P" for > 2 sec. = Display shows controller type (

700

)

-  Key "

" additionally = Software version is displayed 

Manual controller "wake-up"

If the controller is switched off via interface (e.g. from a PC), the display shows 

"

oFF

". By holding key "

" for > 3 sec. the controller unit engage.

Reset parameters to factory settings

Switch OFF supply voltage, press and hold "P"-key, switch supply voltage 

ON again. Code request "C" appears. Enter "88", confirm by "P". One by 

one software version, date and "def" appear. With this, all values are reset to 

factory settings. 

Please note Safety Instructions !

When replacing older types please note 

changed functions and connectors!

Please read these instructions carefully before applying power. Your attention is drawn to 

the fact that the warranty is subject to the application of power sources that are within the 

limits specified in this manual. This documentation was compiled with utmost care, however, 

we cannot guarantee for its correctnesss in every respect. Technical details can be changed 

without notice, especially the software. Please note that the described functions are only 

valid for units containing the software with the version-number shown on page 1. Units with 

an other software number can work a little bit different. You will find this software number 

on the label of the unit too.

ELREHA GmbH

D-68766 Hockenheim, Germany, 

Schwetzinger Str. 103

phone (+49)(0) 6205/2009 -0 | fax -39 | [email protected]

Technical Data 

(see parameter listing for more information)

Supply Voltage...........................................................................see above

Output Relays ...................................................................4x potential free

Contact Rating ...................................... 8A resistive, 3A cos phi 0,4, 250V AC

  TAR 1700-2 (UL) ..............................resistive: 120/240V AC, 8A, 30 k cycles

   

motor: 125/250V AC, ¼ HP,  30 k cycles

Ambient Temperature TAR 1700-2. ...................................-10..+65°C (14..149°F)

Ambient Temperature TAR 3700-2/5700-2. .................... -10..+55°C (14..131°F)

Storage Temperature ...................................................... -30..+70°C (-22..158°F)

Relative Humidity.......................................max. 85% r.H., not condensing

Temperatur Sensor Inputs .......................... 2x TF 201 or TF 501 (Pt1000)

Display ................LED, 7-segment, red, character height 13mm (.51 inch)

Resolution / Accuracy ............................................0,1°C / 0,2°F / typ. ±1K  

Control-/Display Range with Temperature Sensor Types

 

with TF 201 .................................................. -40...+80°C / -40...176°F

 

with TF 5xx (depending on type) up to ..-100...+300°C / -148...572°F

Data storage parameters ..................................................................

$

20 years

Relay indicators ......................................................................... 3 mm, red

Analog Output..........................................................0-10V DC, max. 3 mA

Analog Output Resolution......................... 8 bit within the set benchmarks

Interface............................................................................

E-Link

 (RS-485)

Electrical connection.............................. screw terminals 2,5mm² (.1 inch)

Housing / Protection / Digital Input

 

TAR 1700-2 .........................77 x 35 mm front frame, IP 54 from front 

 

 

Digital input for external, potential free contact

 

TAR 3700-2 ..................................................... for rail mounting, IP 30

 

 

Digital input for mains voltage, 50-60Hz, max. 3mA

 

TAR 5700-2 .........................96 x 48 mm front frame, IP 54 from front

 

 

Digital input for mains voltage, 50-60Hz, max. 3mA

 Accessories 

(please order separately)

-  Temperature sensor TF 201 (up to 80°C max.) 

or

-  Temperature sensor TF 501 (PT1000, up to 300°C, dep. on type)
For type TAR 1700-2: 

-  Matching transformer, please contact us.

ELREHA

TAR

2

1

3

P

4

Blinking: Min.Idle Time of the stage runs

Stage 1

ON/OFF

Stage 2

ON/OFF

Stage 3

ON/OFF

Stage 4

ON/OFF resp. alarm

Increase 

Values

Decrease

Values

Minus

Blinking: 2nd setpoint active

Programming

Key

Blinking: 

Data transfer on bus

Automatic display 

segment test after 

power up !!

Technical Manual 

  

5311032-04/14e

 

 

from Software Vers. 

2.0.1

  Multistage Temperature Controller 

Series:

   

TAR 1700-2

 

TAR 3700-2

 

TAR 5700-2

TAR 1700-2

Panel mounting 

12-24V AC, 50/60 Hz

18-33V DC, 5,5 VA max.

TAR 5700-2

Panel mounting 

230V AC, 50/60 Hz

5,5 VA max. 

TAR 3700-2

Rail mounting 

230V AC, 50/60 Hz

5,5 VA max. 

Blinking = Alarm

ELREHA

TAR

1

2

3

P

4

New Display

Stage 2 

ON/OFF

Stage 3

ON/OFF

Stage 1 

ON/OFF

Stage 4

ON/OFF

Отзывы: