Brief Description
• Suitable as :
Multistage Controller or
Differential Controller with
limitation contacts
• Operating Modes:
4-Stage Controller,
Double 2-Stage Controller,
3-Stage-Cont Alarm,
Differential Controller
• Analog Output 0-10VDC for P/PI-
control or Remote Displays
•
Alarm Limits / Alarm Relay
• Different Sensor Types
• Setpoint shift by Real Time Clock
•
Minimum Idle Time
•
RS-485-Interface
ELEKTRONISCHE REGELUNGEN GMBH
Can be used for
• Cooling, Heating and HVAC
Applications
Operating Elements
Parameters
(setpoints, times, etc.)
All selectable parameters hold a parameter number (e.g. P04), you will find a
listing on the next page.
Calling up and editing
Press key 'P' ...................parameter number appears
Use '
/
' .......................select desired parameter (hold key for autoscroll)
Press "P" again ...............parameter value appears
Use keys '
/
' ................adjust parameter value (hold key for autoscroll)
Press 'P' again ................value is stored, back to parameter no.
Unlock Keys / Access code
To prevent un-authorized persons from editing parameter values, there is a
locking function which allows only the most important parameters to be changed
at any time. All other parameters must be unlocked as follows:
- enter access code before programming at parameter
P41
or
- directly at the parameter to be changed. If a code no. is necessary the
display shows "C00". Set the matching code no. by the "
/
"-keys (70 or
88, see parameter listing) and confirm by "P".
If no key is hit for about four minutes, the access code is cancelled and the
editing function is locked automatically.
After entering of the code '70' the control functions will be disabled.
They will be restartet if the code will be changed manually (e.g. to 88
for other parameters) or will be resetted automatically after 4 minutes
without any press on a button.
Start-up behavior
Directly after start-up the display shows "700" (controller type), after that a
display test passes.
How to find out the controller type
- Press key "P" for > 2 sec. = Display shows controller type (
700
)
- Key "
" additionally = Software version is displayed
Manual controller "wake-up"
If the controller is switched off via interface (e.g. from a PC), the display shows
"
oFF
". By holding key "
" for > 3 sec. the controller unit engage.
Reset parameters to factory settings
Switch OFF supply voltage, press and hold "P"-key, switch supply voltage
ON again. Code request "C" appears. Enter "88", confirm by "P". One by
one software version, date and "def" appear. With this, all values are reset to
factory settings.
Please note Safety Instructions !
When replacing older types please note
changed functions and connectors!
Please read these instructions carefully before applying power. Your attention is drawn to
the fact that the warranty is subject to the application of power sources that are within the
limits specified in this manual. This documentation was compiled with utmost care, however,
we cannot guarantee for its correctnesss in every respect. Technical details can be changed
without notice, especially the software. Please note that the described functions are only
valid for units containing the software with the version-number shown on page 1. Units with
an other software number can work a little bit different. You will find this software number
on the label of the unit too.
ELREHA GmbH
D-68766 Hockenheim, Germany,
Schwetzinger Str. 103
phone (+49)(0) 6205/2009 -0 | fax -39 | [email protected]
Technical Data
(see parameter listing for more information)
Supply Voltage...........................................................................see above
Output Relays ...................................................................4x potential free
Contact Rating ...................................... 8A resistive, 3A cos phi 0,4, 250V AC
TAR 1700-2 (UL) ..............................resistive: 120/240V AC, 8A, 30 k cycles
motor: 125/250V AC, ¼ HP, 30 k cycles
Ambient Temperature TAR 1700-2. ...................................-10..+65°C (14..149°F)
Ambient Temperature TAR 3700-2/5700-2. .................... -10..+55°C (14..131°F)
Storage Temperature ...................................................... -30..+70°C (-22..158°F)
Relative Humidity.......................................max. 85% r.H., not condensing
Temperatur Sensor Inputs .......................... 2x TF 201 or TF 501 (Pt1000)
Display ................LED, 7-segment, red, character height 13mm (.51 inch)
Resolution / Accuracy ............................................0,1°C / 0,2°F / typ. ±1K
Control-/Display Range with Temperature Sensor Types
with TF 201 .................................................. -40...+80°C / -40...176°F
with TF 5xx (depending on type) up to ..-100...+300°C / -148...572°F
Data storage parameters ..................................................................
$
20 years
Relay indicators ......................................................................... 3 mm, red
Analog Output..........................................................0-10V DC, max. 3 mA
Analog Output Resolution......................... 8 bit within the set benchmarks
Interface............................................................................
E-Link
(RS-485)
Electrical connection.............................. screw terminals 2,5mm² (.1 inch)
Housing / Protection / Digital Input
TAR 1700-2 .........................77 x 35 mm front frame, IP 54 from front
Digital input for external, potential free contact
TAR 3700-2 ..................................................... for rail mounting, IP 30
Digital input for mains voltage, 50-60Hz, max. 3mA
TAR 5700-2 .........................96 x 48 mm front frame, IP 54 from front
Digital input for mains voltage, 50-60Hz, max. 3mA
Accessories
(please order separately)
- Temperature sensor TF 201 (up to 80°C max.)
or
- Temperature sensor TF 501 (PT1000, up to 300°C, dep. on type)
For type TAR 1700-2:
- Matching transformer, please contact us.
ELREHA
TAR
2
1
3
P
4
Blinking: Min.Idle Time of the stage runs
Stage 1
ON/OFF
Stage 2
ON/OFF
Stage 3
ON/OFF
Stage 4
ON/OFF resp. alarm
Increase
Values
Decrease
Values
Minus
Blinking: 2nd setpoint active
Programming
Key
Blinking:
Data transfer on bus
Automatic display
segment test after
power up !!
Technical Manual
5311032-04/14e
from Software Vers.
2.0.1
Multistage Temperature Controller
Series:
TAR 1700-2
TAR 3700-2
TAR 5700-2
TAR 1700-2
Panel mounting
12-24V AC, 50/60 Hz
18-33V DC, 5,5 VA max.
TAR 5700-2
Panel mounting
230V AC, 50/60 Hz
5,5 VA max.
TAR 3700-2
Rail mounting
230V AC, 50/60 Hz
5,5 VA max.
Blinking = Alarm
ELREHA
TAR
1
2
3
P
4
New Display
Stage 2
ON/OFF
Stage 3
ON/OFF
Stage 1
ON/OFF
Stage 4
ON/OFF