Functional Description
Display & Sensors
All temperature values can be displayed in °C or °F
with a resolution of 0,1K (0,2°F), selectable by
P21
.
TF201, TF 202 (PTC) as well as TF501 (Pt1000)
sensors can be used, but note that this results in
different temperature ranges. Sensor 2 (Evap. Limit
Sensor) can be disabled.
Temperature Control
The controller compares the actual room tempe-
rature
(P01)
with the control setpoint
(P03)
and
activates the cooling relay which is able to switch
solenoid valves or compressors. The switching
hysteresis (
P09
) prevents the system from short
cycling. An idle time (
P11
) prevents a compressor
from switching ON again immediately.
Setpoint range
With
P07/P08
you can limit the setpoint range to
prevent the end-user from entering critical values.
Switching mode of cooling relay K1
The switching behavior of the cooling relay
(= cooling mode) is defined by parameter
P10
.
2. Setpoint / day-night-shift
(1380-2 only)
To economize energy, e.g. at night, the unit can work
with a second setpoint (
P04
), which can be activated
by the internal time-switch (
P05/P06
).
Emergency Mode of Temperature Control
If the control sensor fails, the unit starts an emer-
gency mode.
The refrigeration relay switches on in
a percentage rate of a total period of 30 minutes,
preset by
P39
.
E.g.: selecting 40% means 12 minutes
on, 18 minutes off.
ParNo. Code
Description
Range
Default
P01
..................x .. x ...x ..x .. Actual temperature control sensor (°C or °F) ......
display only
P02
..................x .. x ...x ..x .. Actual temp. evaporator sensor (°C or °F) ............
display only
P03
..... -- .........x .. x ...x ..x .. Setpoint .................................................................. Low limit P08...high limit P07 .................................................. 0 °C
P04
.... 88 ........... x ........x .. 2nd Setpoint (Night-Setpoint) ............................... ± 100 °C (-148...212 °F) ......................................................... 0
P05
.... 88 ........... x ........x .. Start-up of night-setpoint (in 10 min. steps) ......... 0...235, oFF ............................................................................. oFF
P06
..... 88 ........... x ........x .. Stop of night-setpoint (in 10 minute steps) .......... 0...235, oFF ............................................................................. oFF
P07
..... 88 ........x .. x ...x ..x .. Highest adjustable setpoint .................................. ± 100 °C (-148...212 °F) up to P08 ......................................... +50 °C
P08
..... 88 ........x .. x ...x ..x .. Lowest adjustable setpoint .................................... -100°C / -148°F up to P07 ....................................................... -50°C
P09
..... 88 ........x .. x ...x ..x .. Setpoint hysteresis................................................. 0,0...20,0 K .............................................................................. 2 K
P10
..... 88 ........x .. x ...x ..x .. Switching mode cooling relay ................................ 1= cooling, 2= heating ............................................................ 1
P11
..... 88 ........x .. x ...x ..x .. Cooling relay idle time ........................................... 0...59 minutes .......................................................................... 2 minutes
P12
..... 88 ........x .. x ...x ..x .. Fan operation threshold ......................................... -100°C... +100°C (hyst. 3K fixed) ............................................ 50°C
P13
..... 88 ........x .. x ...x ..x .. Fan operating mode .............................................. 1=, 2=, 3=, see text .................................................................. 1
P14
..... 88 ........x .. x ...x ..x .. Fan delay after defrost ........................................... 0...30 minutes .......................................................................... 3 minutes
P15
..................x .. x ...x ..x .. Remaining minutes till defrost ends ......................
display only
P16
..................x .. x ...x ..x .. Remaining minutes to activate cooling .................
display only
P17
..................x .. x ...x ..x .. Remaining minutes to start fan relay.....................
display only
P18
..................x .. x ...x ..x .. Remaining minutes up to an alarm .......................
display only
P19
..... 88 ........x .. x ...x ..x .. Calibration control sensor ...................................... +/-10,0 K/F ............................................................................... 0 K
P20
..... 88 ........x .. x ...x ..x .. Calibration evap. sensor, resp. sensor OFF ...........+/-10,0 K/F, oFF ....................................................................... 0 K
P21
.....
70
.......x .. x ...x ..x .. Sensor type / °C or °F / measuring range ............. 1= TF 501 / °C / -110...+120°C ................................................ 2
2= TF 201 / °C / -55...+105°C
3= TF 501 / °F / -166...248°F
4= TF 201 / °F / -67...221°F
5= TF 202 / °C / -55...+105°C
6= TF 202 / °F / -67...221°F
P22
..... 88 ........x .. x ...x ..x .. Defrost termination temperature in °C or °F ......... 0,0...30,0°C / 118,0°F .............................................................. 10°C
P23
..... 88 ............ x ........x .. Defrost type (independent from P10) .................... 1= electric, 2= hot gas, ............................................................ 1
3= eAZV, 4= hot gas+AZV (AZV with 1380-2 only)
P23
..... 88 ........x ........x ....... Defrost type (independent from P10) .................... 1= heater by cyclic timer, 2=hot gas by cyclic timer, ............... 1
3= heater by machine runtime, 4= hot gas by mach.runt.
P24
..... 88 ........x ........x ....... Defrost cycle .......................................................... 1...99 hours .............................................................................. 4 hours
P24
..... 88 ............ x ........x .. Defrost event # 1, 000...235, oFF ......................... (1.+.2 position = hours, ........................................................... oFF
P25
..... 88 ............ x ........x .. Defrost event # 2, 000...235, oFF ......................... 3.position = minutes x 10) ....................................................... oFF
P26
..... 88 ............ x ........x .. Defrost event # 3, 000...235, oFF ......................... " ................................................................................................ oFF
P27
..... 88 ............ x ........x .. Defrost event # 4, 000...235, oFF ......................... " ................................................................................................ oFF
P28
..... 88 ........x .. x ...x ..x .. Defrost safety operation time ................................ 0...120 minutes ........................................................................ 30 min.
P29
..... 88 ........x .. x ...x ..x .. Drain time, refrigeration delay after defrost ........... 0...99 minutes .......................................................................... 0 min.
P30
..... 88 ........x .. x ...x ..x .. Alarm Mode, Fan Relay Configuration .................. 0= Alarm relay active ON (N / O)............................................. 1
x .. x ...x ..x ................................................................................... 1= Alarm relay active OFF (N / C)
.........x ..x ................................................................................... 2= like "0", but internal beeper off
.........x ..x ................................................................................... 3= like "1", but internal beeper off
x .. x ...x ..x ................................................................................... 4= Alarm relay resettable within alarm range (see text)
... x .............................................................................................. 5= Rel.4 switches with setpoint 2, alarm by LED only
.........x ..x ................................................................................... 5= Alarm relay configured as fan relay ................................... 5
P31
..... 88 ........x .. x ...x ..x .. Alarm delay ............................................................ 1...99 minutes (if sensor fails < 1 flashing displ.) ......... 5 minutes
P32
..... 88 ........x .. x ...x ..x .. Alarm high limit temperature (relative to P03) ...... 0...100 K (0...100°F) ............................................................... 100K
P33
..... 88 ........x .. x ...x ..x .. Alarm low limit (absolute value) ............................. ± 100 °C (-148...212°F) .......................................................... -100°C
P34
..... -- ............. x ........x .. Clock: hours
P35
..... -- ............. x ........x .. Clock: minutes
P36
..... -- ............. x ........x .. Clock: seconds
P37
..... -- ............. x ........x .. Manual defrost ....................................................... "
"= Start defrost, "
"= Terminate
P38
..... 88 ........x .. x ...x ..x .. "Display Hold" (DH) while defrost event ................ 0 = OFF, 1 = ON ...................................................................... 0
P39
..... 88 ........x .. x ...x ..x .. ON-time of the control relay while sensor error
(Emergency Mode, based on 30 min. interval) ..... 0...100% ................................................................................... 50
P40
..................x .. x ...x ..x .. Current error + error listing .................................... Multiple errors present: Use "
/
" to read
P41
..... no ........x .. x ...x ..x .. Access Code .......................................................... 0...99......................................................................................... 0
Please note the different code for
changing sensor type.
Default values are factory set.
1= cooling
2= heating
warm
activated
de-activated
cold
se
tpo
int
hys
ter
es
is
se
tpo
int
cold
hys
ter
esi
s
warm
de-activ.
activated
O N
30 minutes
Emergency Mode
in
%
Cooling OFF
Cooling ON
O F F