background image

Temperature alarm

A temperature alarm is indicated by:

•  A LED at the front

•  An internal beeper 

  (TAR 1370H-2/TARN only)

•  An alarm relay

  (TARN-Types: Only if the fan relay is not 

  in use).

If  the  temperature  measured  by  the  control 

sensor  exceeds  the  range  set  by 

P32/P33, 

P18

  shows  the  remaining  time  until  an 

alarm occurs.

 

After the delay timer  

P31

 is 

run down, the alarm relay will be activated. 

P32

 is an alarm offset located relative to the 

current setpoint 

P03 

resp. 

P04

, so if the setpoint 

is shifted, the offset remains constant. 

If the alarm mode P30 is set to '4', the alarm 

relay can be reset while the temperature is 

located within the alarm range. This is usable 

e.g. to switch an external signal horn. If the 

temperature comes back to the working ran-

ge, the relay will be reset automatically.

Alarm relay / Beeper Operation Modes

Parameter 

P30

 fixes the alarm relay mode:

 

0

 = Alarm relay active ON

1

 = Alarm relay active OFF

= like 0, but internal beeper off 

     (TARN only)

= like 1, but internal beeper off 

     (TARN only)

4

 = Alarm relay can be reset while 

     temperature is located within the alarm 

     range. Can be used e.g. to switch an  

     external horn.

5

 = Continuous ON of alarm relay if 

     control setpoint 2 is activated 

     (TARN 1380-2 only). Alarm messages  

     will be forwarded by alarm-LED only.  

     Function to switch light by time control. 

5

 = The alarm relay output works as fan 

     relay (TARN types only).

Alarm Beeper 

(1370H-2 and TARN only)

These types contain an integrated beeper 

(can be disabled by P30), which is activated 

with the alarm output. The beeper can be 

reset by any keypress.

Defrost

The  unit  is  equipped  with  a  defrost  relay. 

There is no need for external interlocking the 

defrost output with the cooling output since 

the temperature controller is disabled while 

defrost. For information there is 

P15

 showing 

the  remaining  time  of  the  existing  defrost 

event until termination by time. 

Defrost by Real time clock 

(1380-2 only)

This type contains a real time clock with 6 

settable times, which allows you to initiate four 

defrost events a day and to switch to 'night'-

setpoint. The timer has a power backup for 

about 10 days in case of power failure. The 

clock time can be set by parameters 

P34

 

and 

P35

 (minutes). 

Because the display has only three digits, the 

time value comes in the following format: 

The defrost times are set by 

P24

 - 

P27

 in 

10 minute increments in a 24 hour (military) 

format.  

Example: 13.20 = 01:20 p.m.

Switch times can be de-activated by setting 

to '

oFF

'. The second setpoint depends on 

P05/P06

.

Defrost Modes of the 1380-2 types

P23

  determines  the  defrost  mode,  which 

works independent from the control relay.
1 =

 Heater or Airflow Defrost 

     - Defrost relay active ON 

       (= defrost heater ON)  

 

     - Cooling relay switches OFF. 

2 = 

Hot Gas Defrost 

     - Defrost relay act. ON 

       (= bypass valve open)  

 

     - Cooling relay keeps the solenoid 

       valve open

3 =

 Heater or Free Airflow D (

AZV

)

     Relay characteristic like = 1.

     Addtional generated defrost events. 

4 = 

Hot Gas D (

AZV

     Relay characteristic like = 2.

     Addtional generated defrost events.

3rd Position=

minutes x 10

1st. and 2nd 

Position =

 hours

Defrost time doubling

 (AZV

, 1380-2 only

)

This  is  a  simple  function  to  double  the 

quantity  of  the  potential  defrost  events  (4 

—>  8).  The  unit  generates  new  defrost 

times automatically by adding 12 hours to 

existing times.

Example:

If  a  defrost  cycle  is  fixed  at  14:30,  an 

additional  cycle  starts  at  2:30am  without 

entering this time.

Defrost by Cyclic Timer

 (1370(H)-2 only)

P24 

determines the interval time up to the 

next  defrost  event, 

P28 

fixes  the  defrost 

duration. The cyclic timer starts with power-

up of the TAR, the first (automatic) defrost 

event is possible first after the end of the 

first interval time.

Defrost  modes  of  the  types  1370-2, 

1370H-2)

P23 

fixes the defrost mode.

1 = 

Heater/Airflow Defrost by Cyclic Timer 

     - Defrost relay act. ON 

       (= defrost heater ON)  

 

     - Cooling relay switches OFF. 

2 = 

Hot Gas Defrost by Cyclic Timer

     - Defrost relay act. ON 

       (= bypass valve open)  

 

     - Cooling relay keeps the solenoid 

       valve open

3 = 

 Heater/Airflow Defrost by 

     Machine Runtime

     Like 1, but depending on the added  

     ON times of the cooling relay.

4 = 

Hot Gas Defrost by Machine Runtime

     Like 2, but depending on the added  

     ON times of the cooling relay.

Manual Defrost

•  At parameter 

P37

 by key "

"  

or

•  While the actual temperature can be read  

  on the display, by holding key "

" key for

   more than 2 sec.
Defrost Termination

• 

Thermal termination

  Defrosting  will  be  terminated  whenever 

  the evaporator sensor temperature (

P02

)  

  exceeds  the  temperature  limit  set  with  

  parameter 

P22

• 

Termination by (safety) time

.

  The time set with parameter

 P28

 is the  

  maximum time a defrost cycle can last 

  before it is terminated automatically. 

• 

Manual termination

.

  With parameter 

P37

 you can terminate a  

  defrost cycle by pressing "

" key.  

or

  While the actual temperature (

P01

) can  

  be read, a defrost event can be terminated  

  by holding "

" key for more than 2 

  seconds.

•  If  the  defrost  limit  sensor  is  interrupted,  

  the defrost event will be stopped immedi-

  ately.  

 

After the defrost event is terminated, a drain 

time 

P29

  delays  the  begin  of  the  cooling 

function. 

P16

 shows the remaining time until 

cooling starts again.  

(DH) Display Hold-Funktion

The 

DH 

function can be initiated by 

P38

It  holds  the Actual  Value  Display  while  a 

defrost  event.  During  defrost  the  display 

shows the last measured actual value before 

defrost start. After defrost termination: If the 

actual value is higher than the stored display 

value, the display keep unaltered for further 

15 minutes max. If the actual value falls 2K 

below the stored display value, the display 

shows the actual value again. 

Evaporator Fan Control

Fan operation modes can be selected by 

P13

At TARN-types the alarm relay output can be 

selected (by 

P30

) as fan relay alternatively.

1 = 

Fan runs if cooling output is active.

 

     With defrost termination the fan output 

     is OFF until the Fan Delay Time (

P14

     is run down.  

2 =  

Fan runs continously, except during  

     defrost and Fan Delay Time (

P14

) after  

     defrost. 

     Fan trailing: The fan stops if the temp- 

     erature at the evaporator sensor exceeds  

    

P12

3 = 

Fan runs if the compressor output is on,  

     and during defrost

.    

     The temporal fan delay must be set 

     to "0".  

 

For all 3 fan operation modes at the 

same time there is a thermostatic fan 

delay active, because the fan starts  

only if the evaporator temperature falls  

3K below P12. If this function is not desi-

red, P12 can be set to its upper threshold 

to make it inefficient.

After the end of a defrost cycle

A temporal fan-ON delay is active after a 

defrost event (

P14

). While drain time (

P29

the fan remains stopped.

(

P17

) informs about the remaining time until 

the fan starts again.

Practical conditions

If you want to realize a thermostatic delay, 

select fan mode 

2

 and adjust setpoint 

P12

.

If you want to realize a thermostatic delay 

and airflow defrost, please realize a parallel 

connection of fan relay and defrost relay.

 CONNECTION INFORMATION & SAFETY INSTRUCTIONS

The guarantee will lapse in case of damage caused by failure 

to comply with these operating instructions! We shall not be 

liable for any consequent loss! We do not accept liability for 

personal injury or damage to property caused by inadequate 

handling or non-observance of the safety instructions! The 

guarantee will lapse in such cases.
This  manual  contains  additional  safety  instructions  in  the 

functional description. Please note them!
If you notice any damage, the product may not be connected 

to mains voltage! Danger of Life!

A riskless operation is impossible if:

• The device has visible damages or doesn't work

• After a long-time storage under unfavourable conditions

• The device is strongly draggled or wet

• After inadequate shipping conditions
• Never use this product in equipment or systems that are  

  intended to be used under such circumstances that may  

  affect human life. For applications requiring extremely  

  high reliability, please contact the manufacturer first.
• 

The product may only be used for the applications  

  described on page 1.
•  Electrical installation and putting into service must be  

  done from qualified personnel. 

• 

 During installation and wiring never work when the 

  electricity is not cut-off ! Danger of electric shock!

• 

 Never operate unit without housing. 

  Danger of electric shock!

•  

All ‘PE’ terminals must be connected to ground.  

  Danger of electric shock! 

Without PE the internal noise  

  filter will not work, faulty indicated values may occur.
•  Please note the safety instructions and standards of your  

  place of installation!
•  Before installation: Check the limits of the controller and  

  the application (see tech. data). Check amongst others:

  - Make sure that all wiring has been made in accordance  

    with the wiring diagram in this manual.

  - Supply voltage (is printed on the type label).

  - Environmental limits for temperature/humidity. 

  -  Maximum admitted current rate for the relays. Compare  

    it with the peak start-up currents of the controlled loads 

    (motors, heaters,etc.). 

 

  Outside these limits malfunction or damages may occur.
•  Sensor/probe cables must be shielded. Don’t install them  

  in parallel to high-current cables. Shielding must be  

  connected to PE at the end close to the controller. 

  If not, inductive interferences may occur. 
•  Please note for elongation: The wire gauge is not critical,  

  but should have 0,5mm² as a minimum.
•  Mounting the controller close to power relays is    

  unfavourable. Strong electro-magnetic interference,  

  malfunction may occur!
• All used temperature sensors must be identical. Never  

  use different types at the same time. This will not work.
•  TF-type sensors are not designed for being immersed in  

  fluids permanently. In such a case, always use dip-fittings.  

  With extreme temperature variations, the sensor may be  

  damaged.

Cleaning

 

The use of a dry, lint-free cloth is sufficient to clean the product. 

Never use liquids or acidic fluids!  Risk of damage!

Danger

Notice

Caution

Отзывы: