Product Description / Applications

•  Controller for humidification and dehumidify

•  For single or network operation  

•  Connection to the Compound System VPR 5240-2

•  3 Humidity Sensor Inputs, 3 Relays, 2 Digital Inputs, 

  Analog In-/Output 0-10V / 4-20mA 

•  Connection of Remote Displays of the TAA xx15 series

Standard Functions

•  Dual Setpoint Control

•  Control via Analogue Output 

•  Alarm Limits 

•  Day-/Night Operation 

•  Assignment to Compounds

Please note safety instructions !

 Operating / Operating Elements

Programming

All parameters of the 

EVP

 are distributed on different pages.

While normal operation or if no key is pressed for about 3 minutes, the 

EVP

displays the following information:
1st priority: ...............current failure (blinking)

2nd priority:  .............operating states (e.g. ‚oFF‘)

3rd priority:  ..............selected ‚permanent parameter‘ display

Selecting and Changing of Parameters
Key 

Action

P

 (> 2 sec.)  .............Page name will be displayed



  ..........................Select desired page 

P

    ...........................Enter the page



  ..........................Select parameter 

P

    ...........................Prepare programming. Enter access code if necessary



  ..........................Change value

 

 

If you hold the key, the values change faster and faster

P

   ...........................Confirm programming

P

 (> 2 sec.)  .............Page name will be displayed again

Technical Manual 

5311437-04/01E

2

 

Humidity Controller

 

from SoftwVers. 

1.01  

 

Type: 

 

EVP 3260

ELEKTRONISCHE  REGELUNGEN  GMBH

Parameter Pages

P

(L)

> 2 sec.

Actual 

Values 

Page

P

(r)

Setpoint

Page

(P)

Mode

Page

(h)

Assign-

ment 

Page

L01

r01

P01

h01

1. Parameter 

on the: 

P

P

P

Access Protection

Except the temperature setpoints, parameters can be changed only after 

entering a correct access code. If you want to change such a parameter 

after pushing the „P“-key, then the following display appears:

Now the controller expects the entry of a code number. 

This code number is always 88. Enter it by the up/down 

keys and confirm it by pressing „P“ again.

If no key is pushed for about 3 minutes, the code number must be 

entered again.

88

(00

increase

values

decrease

values

The currently displayed

setpoint is active

In controllers which contain older software

versions, some functions may not be available !

1

2

3

4

EVP

ELREHA

P

3 keys allow programming the unit, all parameters will be displayed on

the red LED-7-segment display. 3 red symbols at the right side indicate

specific control functions (

not the relay states, these are displayed on the

‚Actual Page‘ !

).

With a requested relay output, but not elapsed min. idle time, the appropri-

ate relay will not be activated. 

The affiliated icon is blinking while min. idle is running.

LED on = dehumidify

LED blinking 

  = Min. idle time

Programming Key

LED blinking = Alarm

LEDs  

       are blinking the same time =

control functions are disabled by digital input or via interface.

LED on = humidification  

LED blinking 

   = Min. idle time

The current states of the digital inputs, the relays and the data trans-

mission can be read on the Actual Values Page under L60 and L61.

EVP

P

ELREH A

Содержание EVP 3260

Страница 1: ...int Page P Mode Page h Assign ment Page L01 r01 P01 h01 1 Parameter on the P P P Access Protection Except the temperature setpoints parameters can be changed only after entering a correct access code...

Страница 2: ...After a long time storage under unfavourable conditions The device is strongly draggled or wet After inadequate shipping conditions Never use this product in equipment or systems that are intended to...

Страница 3: ...the controller the display will indicate the permanent parameter after some seconds or in case of a failure it will display the current failure This can also be read if you don t touch a key for more...

Страница 4: ...oFF switched off from the VPR 0 1 off L43 X Day Night Mode 0 day 1 night 0 1 L44 X Operation state of the controller on off L50 X Current value of the analogue output in X of the selected range 0 100...

Страница 5: ...ht operation active low dnK night operation active high ofl unit oFF active low ofK unit oFF active high tol dehumidifiy oFF active low toK dehumidifiy oFF active high bol humidification oFF active lo...

Страница 6: ...resis humidification Setpoint dehumidify Setpoint humidification Night setpoint dehumidify Night setpoint humidification Setpoint dehumidify Hysteresis dehumidify 100 0 Setpoint humidification Hystere...

Страница 7: ...ity Dimensions Connection 1 2 3 4 1 2 8 3 4 5 7 6 12 11 9 13 10 22 EVP 20 21 27 23 24 25 26 28 32 29 31 30 105 4 13 46 1 81 63 2 48 91 3 58 115 4 53 19 15 18 14 16 17 ELREHA P 38 37 34 33 35 36 analog...

Отзывы: