Chapter Four
Configuration
Page
49
Switch
Function
Equivalent Hayes Command at
start-up.
0000
Normal Operation – no change
0100
Restore Factory Defaults.
AT&F
Baud rates
1100
Perform Transmit BER Test
AT&T0 (for use with AT&T1 at
other module - see section 6.2.1)
Serial
Radio
0010
Transparent Mode.
AT&M0B0C4&L1
9600
19200
1010
“
AT&M0B1C6&L1
19200
57600
0110
“
AT&M0B1C9&L1
38400
57600
1110
“
AT&M0B2C10&L1
57600
115200
0001
Fast Controlled Mode, Auto-
connect master.
AT&M3&U1B0C4&E1&Z0=2&
L2
9600
19200
1001
“
AT&M3&U1B1C6&E1&Z0=2&
L2
19200
57600
0101
“
AT&M3&U1B1C9&E1&Z0=2&
L2
38400
57600
1101
“
AT&M3&U1B2C10&E1&Z0=2
&L2
57600
115200
0011
Fast Controlled Mode,
Auto-connect slave.
AT&M3&U2B0C4&E1&L3
9600
19200
1011
“
AT&M3&U2B1C6&E1&L3
19200
57600
0111
“
AT&M3&U2B1C9&E1&L3
38400
57600
1111
“
AT&M3&U2B2C10&E1&L3
57600
115200