Microwave Motion Detector
ORDER CODE Description
PS-RS02
Microwave motion detector
Setting sensitivity (range)
The range is the distance of the circular detection
zone produced on the ground in an open area
adjacent to where the PS-RS02 sensor is mounted.
Minimum range
— (approx. 2m) — is achieved with
the sensitivity control turned fully anticlockwise.
Maximum range
— (approx. 10m) — is set with the
control turned full clockwise.
Note:
The above detection distances are based on a
person who is between 1.6 m/1.7 m tall moving at
a speed of 0.6 – 1.5m/sec. Detection range will differ
depending on the height and stature of a person
moving within the detection zone and reduced if
detecting movement through building structures
(glass, partitions, etc.).
Time ‘On’ setting
S
The luminaire can be set to stay ON for any period
of time between approx. 8sec (control turned fully
anticlockwise) and a maximum of 12min (control
turned fully clockwise).
Any movement detected before the set time has
elapsed will re-start the timer therefore holding the
lighting on.
Note:
After the light switches OFF, it takes approx.
1 sec before the sensor will start detecting movement
again.
Daylight control setting
The light response threshold can be adjusted from
approx. 2 Lux to 2000 Lux. Rotate the control fully
anti-clockwise to select dusk-to-dawn operation at
about 2 lux. Turn it fully clockwise to select daylight
operation at about 2000 lux.
Set-up/walk test
Set the Time ‘on’ control to minimum (fully
anticlockwise) and the Daylight control to maximum
(fully clockwise) to adjust the sensitivity /range. Adjust
the Sensitivity control, walk in the required detection
area then re-adjust until the area is correctly
monitored. Then adjust the daylight control to suit an
appropriate ambient light level and finally set the ‘on’
time
(NB: with fluorescent lamps it is advisable to let them
operate for approx. 10minutes from each start).
Note:
Adjust the rotational controls with care because
the three potentiometers are connected directly to a
PCB.
The 'stops' built into each of these components can
easily be damaged.
INSTALLATION
L — Live Supply
L — Live (output to load)
N — Neutral
Sensitivity (range)
Time ‘On’ setting
Daylight control
Light sensor