VII. Configuration Level
Display
Parameter
Display
"Process"
„Set“
ConF Controller configuration
2P h
2-point- or continuous-
controller „heating“ (ex works)
2P c
2point-controller or Continuous-
controller „cooling“
2Pnc
2point-controller or Continuous-
controller „cooling“
with non-linear cooling*)
3P
3-point controller: "heating - off - cooling"
3Pnc
3-point controller: "heating - off - cooling"
cooling mode with non-linear cooling*)
3PSt
3-point-step-
controller „on-neutral-off“
*) Cooling action can be pre-selected with either linear or
non-linear cooling response curve ( e.g. for vapour cooling).
Out1
Configuration Output 1
OFF
OUT 1 not active
Controller output
rEL.
Relay (ex works)
biSt.
bistable voltage signal
Out2
Configuration Output 2
OFF
OUT 2 not active
Controller output or
rEL.
Relay (ex works)
alarm (A2) output
biSt.
bistable voltage signal
Out4
Configuration Output 4
OFF
Output OUT4 not active
Only version: R1300-2
and version: R1300-3
if ConF= 2Ph:heating, ConF= 2Pc: cooling, ConF= 2Pnc: cooling
if ConF= 3P :heating, ConF= 3Pnc:heating
Co.h0 Control output: 0...20mA / 0...10V
Co.h4 Control output: 4...20mA / 2...10V
if ConF= 3P :cooling, ConF=3Pnc:cooling
Co.c0 Control output: 0...20mA / 0...10V
Co.c4 Control output: 4...20mA / 2...10V
Only version: R1300-3
Pr. 0 Process value output: 0...20mA / 0...10V DC
Pr. 4 Process value output: 4...20mA / 2...10V DC
SP. 0 Analogue setpoint output: 0...20mA / 0...10V DC
SP. 4 Analogue setpoint output: 4...20mA / 2...10V DC
Out5
Configuration Output 5
OFF
Output OUT5 not active
Only version: R1300-3
if ConF= 2Ph:heating, ConF= 2Pc: cooling, ConF= 2Pnc: cooling
if ConF= 3P :heating, ConF= 3Pnc:heating
Co.h0 Control output: 0...20mA / 0...10V
Co.h4 Control output: 4...20mA / 2...10V
if ConF= 3P :cooling, ConF=3Pnc:cooling
Co.c0 Control output: 0...20mA / 0...10V
Co.c4 Control output: 4...20mA / 2...10V
Pr. 0 Process value output: 0...20mA / 0...10V DC
Pr. 4 Process value output: 4...20mA / 2...10V DC
SP. 0 Analogue setpoint output: 0...20mA / 0...10V DC
SP. 4 Analogue setpoint output: 4...20mA / 2...10V DC