Manual: R1300-X-00-X_EN Release: 1.04 © Elotech GmbH Page 14/20
Display
Parameter
Display
"Process"
„Set“
Only if 1 P = OFF :
1 Sd control sensivity heating
OFF; 0,1... 80,0 units (°C/°F)
(ex works: 0,1)
OFF; 0,01... 8,00 units
OFF; 0,001...0,800 units
Sd = 10,0
on
off
-5,0
+5,0
Setpoint
Process
The following parameters apply only to the configuration of heat-cool controllers:
Sh
switch-point difference
OFF; 0,1...80,0
units
(ex works: OFF)
OFF; 0,01...8,00
units 1)
OFF; 0,001...0,800
units 2)
This parameter raises the setpoint (switch-point) for cooling output
by the displayed value. It can be help to reduce the switching
frequency between the heating and cooling outputs, if this is to
high.
Simultaneously activation of heat and cool outputs is not possible.
2 P
OUT2 / OUT5- cooling
OFF; 0,1...100,0 %
(ex works: 6,0)
prop.-band (P)
if Xp = OFF,
the next parameter to follow is „2 Sd“ = control sensitivity OUT 2
2 d
OUT2 / OUT5 - cooling
OFF; 1...200 secs
(ex works: 150)
rate (D)
2 J
OUT2 / OUT5 - cooling
OFF; 1...1000 secs
(ex works: 15,0)
reset (I)
2 CY
OUT2 / OUT5 - cooling
cycle time
0,5...240,0 secs
(ex works: 10,0)
Only if 2 P = OFF :
2 Sd control sensivity
OFF; 0,1...80,0
units
(ex works: OFF)
cooling
OFF; 0,01...8,00
units 1)
OFF; 0,001...0,800
units 2)
Opt
self tuning
see next pages please