background image

ELOE06GZKE001 

 

!!!CAUTION!!! 

 
Unless  otherwise  specified  on  the  product,  as  for  permissible  over-voltage,  the 
converter  can  be  used  in  the  environments  where  lightning  over-voltage  is  not 
necessary  to  be  considered.  Converters  connection  to  the  lines  exposed  to  the 
atmospheric  electricity  influences  is  prohibited  unless  separate  line  protection  is 
carried out e.g. via very fast lightning arrestor. 
 

5.0 

Testing 

When the supply is switched on, connect positive terminal to the 3 contact and the 
negative terminal to the 5 contact of the DC power supply of 5 to 9 V on the RS-
232 connector. The voltage of c. 2 - 3V has to be on the 3-8 contacts of the RS-
485 connector. 

6.0 

Troubleshooting 

 
 

Symptom 

Action 

   Converter does not work 

Check if the link is connected properly 

   after installation 

Check if 3-8 contacts are not changed 

 

Check the power supply. 

 

Check RS-232 connection and RTS polarity. 

                                                   Check if the time constant selection is right.  
 

 

 

  Connection in normal 

Check the power supply 

  operation quit working 

Check the cable connection 

   

Use the test as with 5.0 

 

 

 

 

7.0 

Ordering information  

Supply code is ELO E06G.  
Ordering code for power supply is ELO E0Q4. Supply connector (for cable) can 
be supplied separately. 

Содержание E06G

Страница 1: ...RS 232 RS 485 Converter with HW and Automatic Control without Galvanic Isolation of the Interface ELO E06G Operation manual ...

Страница 2: ...ace range is limited to 15m distance RS 485 interface signals transmission enables to increase communication range transmission interference immunity and communication partners number 1 1 Use of the converter The converter increases transmission immunity against electrical disturbance but not against atmospheric electricity influences To lead the cable outside buildings it is necessary to provide ...

Страница 3: ...τ of RTS switching off or TxD return to the neutral polarity Time interval length τ has to be dependent on applied transmission rate because in the automatic mode there it is necessary to keep the transmitter active for the period equal to one byte transmission time In the automatic mode every device that is to transmit has to wait at least for the time τ from the last byte recorded on RS 485 bus ...

Страница 4: ...an be connected via bus see fig with up to 32 partners The RS 485 connector description and the internal passive terminator Contact 1 2 3 4 5 6 7 8 9 Signal TAU1 TAU2 TxRx RTSpol GND TAU3 T TxRx Supp Internal terminator 1k5 Totally correct RS 485 bus handling is shown in the picture RS 485 link must be termina ted at both ends The resistors called passi ve terminators must be connected between A a...

Страница 5: ...nal resistor 680 Ω jumper 7 3 and one external resistor 680 Ω between 5 and 8 contacts 3 3 Converter setting To work properly the converter needs time out setting τ For this case there are contacts TAU1 TAU2 and TAU3 numbers 1 2 and 6 on the RS 485 connector How to use them is shown at the table below Data rate 2 1 6 4800 not used not used not used 9600 not used 19200 not used 56k 38400 not used 2...

Страница 6: ...tant 0 1 to 2 5 ms Power supply external DC supply 6 24V 100mA Minimum max supply voltage 6 24 V Connector EIAJ 2 35mm and RS 485 connector Isolation between interfaces without galvanic isolation Permissible over voltage on the the line must not be exposed to the line under ČSN 33 0420 atmospheric discharge influences Required link impedance 100Ω 4 2 Other Range 1200m double wire link Maximum tran...

Страница 7: ...e terminal to the 5 contact of the DC power supply of 5 to 9 V on the RS 232 connector The voltage of c 2 3V has to be on the 3 8 contacts of the RS 485 connector 6 0 Troubleshooting Symptom Action Converter does not work Check if the link is connected properly after installation Check if 3 8 contacts are not changed Check the power supply Check RS 232 connection and RTS polarity Check if the time...

Страница 8: ...ELOE06GZKE001 8 ...