8. FUNCTIONS SETUP

To setup module functions, use the dipswitch indicated in “OVERVIEW AND WIRING DIAGRAM” on

page 4.

Functions are listed in the following table:

Note: when 1OASBOX module relay output is set to control optical-acoustic devices over supervised control

lines, the module will be detected as a 

bell control module 

and the related output can be silenced from the con-

trol panel.

9. DISPOSAL INSTRUCTIONS

Dispose of analogue addressable module 1OASBOX  in compliance with current city regulations and by lea-

ving the device in a dumping ground that is authorized for the disposal of electronic products.

If required, please contact the appropriate city office for additional information.
The materials used for this product are very harmful and polluting if dispersed in the environment.

Dip Switch

Position

Function

1

ON

Not used.

2

ON

Not used.

3

ON

Relay output contacts are free from potential

(set dip switch 5 and 6 to OFF)

OFF

Relay output is set to control optical-acoustic devices over supervised 

control line

(set dip switch 5 and 6 to ON)

4

ON

Not used.

5

ON

Set it to ON (also dipswitch 6) when dipswitch 3 is set to OFF

OFF

Set it to OFF (also dipswitch 6) when dipswitch 3 is set to ON

6

ON

Set it to ON (also dipswitch 5) when dipswitch 3 is set to OFF

OFF

Set it to OFF (also dipswitch 5) when dipswitch 3 is set to ON

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание 10ASBOX

Страница 1: ...1 Output Analogue Addressable Module 1OASBOX TECHNICAL MANUAL CPD certification n 0051 CPD 0276 www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...ed is subjected to faults just as any other electronic or mechanic pro duct As this item is meant to protect both property and people we invite the user to proportion the level of protection that the...

Страница 3: ...onnection does not require an external power supply unit 1OASBOX module is supplied with a reduced dimension plastic housing and is also suitable to be installed on 503 type flush mount boxes 2 TECHNI...

Страница 4: ...strongly recommended not to enable automatic activation function when the output is connected to a device that might cause damage if activated by mistake In this case according to the application the...

Страница 5: ...closing the side fixing clips Please pay attention not to damage the fixing clips when opening the module 6 FLUSH MOUNT DIAGRAM GENTLY RELEASE THE BASE FIXING CLIP UNTIL IT IS FREE FROM THE COVER HOLD...

Страница 6: ...the code to set Please consider that code setup is fundamental for the correct identification of the module from the control panel the module will be detected as one output module or bell control mod...

Страница 7: ...disposal of electronic products If required please contact the appropriate city office for additional information The materials used for this product are very harmful and polluting if dispersed in th...

Отзывы: