PECIFICATION
Input Specification
VRS124000-xP
Voltage (rated)
100-240Vac
Voltage (operating)
90-264Vac
Frequency
50-60Hz
Mains Input Fuse (Terminal)
T2.0A HRC
Module fuse - Mains
T2.0A HRC
Max standby Power
0.5W (no load connected)
Max Mains Input Current
1.5A
Output Specification
Voltage
11.4 – 12.6vdc (12.0vdc nominal)
Max load current
4A
Ripple
150 mV pk-pk max
Module Output Fuse
F4.0A
Load output Fuses
See Model Specification Table below
Overload
Electronic shutdown until overload or short circuit removed
Local Indicators
MAINS LED (Green)
Mains present
FAULT LED (Red)
Fault present: Output fuse fail
(requires load to be connected)
Fused Outputs
Model:
VRS124000-xP
No. of Fused outputs:
1, 2, 4 & 8
Fuse Value:
[as fitted in fused output module(s)]
1 x F4.0A
2 x F2.0A
4 x F1.0A
8 x F500mA
Mechanical
IP68 - Enclosure
Enclosure Dimensions
h x w x d (mm) [external]
250 x 150 x 100
Weight
1.05kg
Environmental
Temperature
-10 to +40°C (operating) 95% RH non-condensing
-20 to +80°C (storage)