Manual | EN

CU8130-0120

Uninterruptible Power Supply (Battery-backed)

1/14/2021 | Version: 1.0

Summary of Contents for CU8110-0120

Page 1: ...Manual EN CU8130 0120 Uninterruptible Power Supply Battery backed 1 14 2021 Version 1 0 ...

Page 2: ......

Page 3: ... 1 Fastening to the DIN rail 18 6 1 2 Installing the mounting plate optional 19 6 2 Power supply 20 6 3 Communication 21 6 3 1 Connection via UPS OCT 21 6 3 2 Connecting additional devices 22 6 3 3 Connection via USB 23 6 3 4 Connection via digital I O 24 6 4 Charging the UPS 25 7 Configuration 26 7 1 Install UPS software 26 7 2 System behavior 27 7 3 UPS configuration dialogs 30 7 3 1 Device conf...

Page 4: ...30 0120 4 Version 1 0 9 1 Replacing the battery module 47 9 2 Cleaning 48 10 Decommissioning 49 10 1 Dismantling the UPS 49 10 2 Disposal 50 11 Technical data 51 12 Appendix 52 12 1 Accessories 52 12 2 Support and Service 53 ...

Page 5: ...products that have already been supplied may be made on the basis of the data diagrams and descriptions in this documentation Trademarks Beckhoff TwinCAT EtherCAT EtherCAT G EtherCAT G10 EtherCAT P Safety over EtherCAT TwinSAFE XFC XTS and XPlanar are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third p...

Page 6: ...jury WARNING Hazard with medium risk of death or serious injury CAUTION There is a low risk hazard that can result in minor injury Warnings relating to damage to property or the environment NOTE There is a potential hazard to the environment and equipment Notes showing further information or tips This notice provides important information that will be of assistance in dealing with the product or s...

Page 7: ...Notes on the documentation CU8130 0120 7 Version 1 0 1 2 Documentation issue status Version Modifications 1 0 First version ...

Page 8: ... that satisfies protection class IP20 This involves finger protection and protection against solid foreign objects up to 12 5 mm but not protection against water Operation of the devices in wet and dusty environments is not permitted The specified limits for electrical and technical data must be adhered to Ensure full functionality and replace the battery module after five years Improper use The U...

Page 9: ...eat up or in the worst case explode The UPS location must be adequately ventilated In case of a fault the UPS can release flammable gases that could cause an explosion Do not store the UPS in an airtight container or bag The battery pack can release gases that could explode if the UPS is kept in an airtight enclosure If you come into contact with electrolyte rinse the affected body part immediatel...

Page 10: ... impacts Therefore during transport please protect your device from mechanical stress and use the original packaging Table 1 Dimensions and weight CU8130 0120 Dimensions W x H x D 60 mm x 100 mm x 90 mm Weight approx 800 g Storage Observe the following storage conditions in order to maintain the service life of the UPS Store the UPS at room temperature or below Do not store the UPS in a dusty envi...

Page 11: ...vailable for communication between the UPS and the Industrial PC A special feature of OCT is that the connecting lines 24 V 0 V between the Industrial PC and UPS are used not only to supply power to the Industrial PC but also for bidirectional modulated data transmission 4 1 Structure Fig 1 Structure of a CU8130 0240 UPS Table 2 Legend for the configuration No Component Description 1 Power supply ...

Page 12: ...Serial number for the unambiguous identification of the product 3 Date of manufacture 4 Maximum power consumption and power output of the UPS 5 UPS capacity 6 Hardware and software version 7 Power supply 24 V DC 8 CE approval 9 Machine readable information in the form of a Data Matrix Code DMC code scheme ECC200 that you can use for better identification and management ...

Page 13: ...UPS which is connected between the AC power supply and the load to be supported always supplies at least 24 V at the output due to a step up converter If the input voltage drops below this value operation is switched to UPS mode and the output is supplied by the energy storage device UPS mode The UPS then continues to supply exactly 24 V In the case of an input voltage from 24 V to 24 V 20 28 8 V ...

Page 14: ...discharge currents Discharge current A Time to switch off s Usable energy Wh 0 5 3750 12 50 1 0 1900 12 67 1 5 1215 12 15 2 0 900 12 00 2 5 650 10 83 3 0 450 9 00 3 5 320 7 47 4 0 200 4 67 4 5 34 1 02 Fig 4 Hold time without temperature and ageing effects Fig 5 Usable energy without temperature and ageing effects ...

Page 15: ...pecially by devices without UPS OCT These include for example older Beckhoff Industrial PCs but also components supplied by third party providers Fig 6 USB 2 0 interface X101 The USB interface is of type B and corresponds to the USB 2 0 specification Table 5 USB interface X101 PIN assignment Pin Connection Typical assignment 1 VBUS Red 2 D White 3 D Green 4 GND Black Shell Shield Drain Wire ...

Page 16: ...mum output current of the UPS Table 7 Power supply X102 right hand connection No Pin Description 4 UPS RDY 0V PE 24 V DC output This output is switched to 24V when the UPS charging is above a set threshold e g 80 5 P FAIL 0V 24 V DC output for power fail signal This output is switched to 24 V if the power supply fails or if P SHDN is activated This output can be connected with the PC_ON input on a...

Page 17: ...Commissioning CU8130 0120 17 Version 1 0 6 Commissioning 6 1 Assembly Fig 8 CU8130 0120 dimensions Fig 9 CU8130 0120 with mounting plate optional dimensions ...

Page 18: ...UPS to the DIN rail as follows 1 First place the UPS against the lower edge of the DIN rail 2 Tilt the upper part of the UPS towards the DIN rail 3 Lightly press the UPS against the DIN rail and upwards ð As soon as you press the UPS upwards the lower springs of the DIN rail adapters give way In this manner the UPS can be attached on the upper edge of the DIN rail 4 Attach the UPS to the upper edg...

Page 19: ...apters and the grounding springs on the rear side of the UPS have to be dismounted The mounting plate is not included in the scope of delivery see Accessories 52 Requirements C9900 M675 mounting plate made of black anodized aluminum Screwdrivers Install the mounting plate as follows 1 Loosen the six M4 screws and remove the DIN rail adapter 2 Loosen the M3 screws and remove the grounding springs f...

Page 20: ...tions and strip lengths Cable cross section 0 5 1 5 mm2 max 1 mm2 with wire end sleeve AWG 20 AWG 16 max AWG 17 with wire end sleeve Strip length 8 9 mm 0 33 inch Connect the UPS as follows 1 Open a spring loaded terminal by lightly pressing the push mechanism with a screwdriver or a mandrel 2 The wire can now be inserted into the round terminal opening without any force 3 The terminal closes auto...

Page 21: ...PS software on Windows 7 or Windows 10 6 3 1 Connection via UPS OCT A special feature of the Beckhoff CU8130 0120 UPS is OCT One Cable Technology as a communication technology between UPS and Industrial PC The two connection cables 24 V 0 V between the Industrial PC and the UPS are used to supply power to the Industrial PC and for bidirectional modulated data transmission Fig 11 Example of a conne...

Page 22: ...ing additional devices If you are supporting an additional device the interfaces U1out and U2out combined must not exceed the maximum output current of the UPS Fig 12 Connection example when using the second USP output U2out for an additional Control Panel ...

Page 23: ... is provided by the USB interface Status data can likewise be retrieved for diagnostic purposes or the UPS configured when communicating via USB Fig 13 Example of a connection via USB with a CU8130 0120 UPS and a CX5240 Embedded PC The USB interface conforms to the USB 2 0 standard The cable length is limited to 5 m ...

Page 24: ...put of an Industrial PC In the event of a power failure the P FAIL output is set to 24 V 24 V are thus applied to the PC_ON input of the Industrial PC and the Industrial PC is shut down properly UPS EN The Power Status output of an Industrial PC can be connected to the UPS EN input of the UPS in order to switch off the U1out and U2out outputs of the UPS in the event of a desired PC shutdown After ...

Page 25: ...n charge the UPS in order to commission or store the UPS in a charged state For this you need a 24 V power supply unit and the Beckhoff UPS Proceed as follows 1 Connect a 24 V power supply to the Uin input of the UPS 2 Switch on the 24 V power supply ð The UPS is charging The DIAG LED flashes green 3 c Charge the UPS completely ð The DIAG LED lights up permanently green as soon as the UPS is fully...

Page 26: ...version of the UPS software is already installed uninstall it first since it may not be possible to update all files Requirements Windows 7 or Windows 10 32 and 64 Bit Installation file available at http ftp beckhoff com download software embPC Control Tools CU81x0 Proceed as follows 1 Close all running applications 2 Start the file Beckhoff_UPSvx x x x exe to install the UPS software 3 Select the...

Page 27: ...ver and affect how long the UPS supports the devices connected to it when notifications or the critical alarm are issued Short power failure tBatt tCA Long power failure tBatt tCA Long power failure during operation tBatt tCA The UPS service has been started and is active During a long power failure the UPS service irrevocably starts shutting down the system ...

Page 28: ... initiates a shutdown and the supply is restored during the shutdown Once the UPS service has initiated the shutdown this process cannot be stopped and must be completed Repeated power failures during the shutdown are bridged by the UPS In order to enable the IPC to restart the external power supply is interrupted briefly a few seconds Value Description Properties tBatt Time during which the syste...

Page 29: ...tem is shut down completely Once this time has elapsed the UPS irrevocably switches off the outputs and the IPC in order to save battery capacity Configurable via the Beckhoff UPS configuration dialog The available values are hardware specific tUPSoff should always be tSDwin tSDsrv Time required by the UPS service for shutting down internal tasks tSDsrv tSDtask tTCstop tSDwin Time required by the ...

Page 30: ... the devices connected to it and the delay time for switching off the UPS Only a user with administrator rights can set the settings of the UPS Status Shows major information about the current power source and battery load information Power fail counter From UPS software version 3 0 0 6 The counter is reset at UPS service start and counts the detected power fails Details Shows current configured U...

Page 31: ...m 120 Available only if User Defined battery type is selected The setting is necessary for instance to be able to calculate the remaining charge available under battery operation Battery replace service interval 0 480 months 60 5 years and checkbox not enabled The user is able to enter configure the battery replace service interval number of months before first warning is logged to Windows eventlo...

Page 32: ...ate to 25 05 12 Shows the suggested service interval update date shown in the Reset service interval command dialog 25 May 2012 Update firmware Starts a firmware update Self test Executes a self test and displays the result OK Test successful the battery is OK BT Failed because the battery capacity was insufficient or because a battery is not even present NG Failed as a result of overload NA Test ...

Page 33: ...n time limit Max time on battery before critical alarm 0 720 min 2 If you have selected this option then the UPS service will issue a critical alarm after the set time and will shut down the PC The critical alarm may however be issued earlier if the battery capacity is exhausted If the value is set to 0 the PC will be shut down immediately in the event of a power failure and the OS shutdown can no...

Page 34: ...default name UPS System Shutdown Program This command is only available under XP operating system The command is only available if the default task is not allready in the task list Please use the task scheduler dialog in the MMC Microsoft Management Console to create new shutdown tasks on Windows Vista or 7 systems Edit UPS Sys tem Shut down Pro gram Displays options that you can configure for a s...

Page 35: ...read out from the device and are placed in the ComboBox The UPS service must be configured and started up with the appropriate UPS model to make this possible Advanced Dialog with advanced shutdown or end session settings for systems without Soft Power Off feature S5 e g NT4 For additional info see Advanced settings dialog This option is not available on systems supporting Soft Power Off feature d...

Page 36: ... in the event of a power failure In the next step define the time after which the ups should switch off its supply outputs Note that the industrial PC must be shut down properly within this period Make sure that you do not set a value that is too low and that the set time covers the entire shutdown process Proceed as follows 1 Start the UPS software and click Select 2 Select Beckhoff USB UPS to co...

Page 37: ...the industrial PC has sufficient time to shut down properly Always plan for a sufficient headroom The outputs of the UPS are irrevocably switched off after the delay time has elapsed even if the power supply returns ð In this example in the event of a power failure the critical alarm is triggered after two minutes and thereafter the Industrial PC is shutting down As soon as the critical alarm is t...

Page 38: ...on The function block FB_GetUPSStatus reads the status of the UPS hardware from the PLC The function block is level triggered which means that the status information of the UPS is only cyclically read while the bEnable input is set To maintain system loading at a low level the status information is only read approximately every 4 5 s When the bValid output is set the most recently read data is val...

Page 39: ...n error It is possible that the UPS is not configured correctly or that no UPS is configured at all 0x8002 Communication error Communication with the UPS was interrupted 0x8003 Error during the reading of the status data stStatus Structure with the status information of the UPS type ST_UPSStatus 40 Not every UPS device can supply all the status information Some devices for example cannot supply th...

Page 40: ...his member can be one or more of th e following values Bits0 7 General battery status flags if all bits are set to 0 unknown status Bit0 High bit set high battery charge Bit1 Low bit set low battery charge Bit2 Critical bit set battery is near empty Bit3 Charging bit set battery is charging Bits4 6 reserved all bits are 0 Bit7 No Battery bit set battery not found or not connected bit not set batte...

Page 41: ... the UPS can not supply this parameter Bat teryLife Time X X None X X X Remaining battery life in minutes The value is al ways zero if the UPS can not supply this parameter eBatteryS tatus BatteryOk BatteryUn knownStatus if no battery exists from UPS soft ware version 2 0 0 6 and UPS firmware 25 1 I BatteryOk BatteryUn knownStatus if no battery exists BatteryOk BatteryUnknown Status when no batter...

Page 42: ...e mented in the UPS software version 3 0 0 8 High bit 0 set if battery is fully charged Charging bit 3 set No Battery bit 7 set if no battery was found No Battery bit 7 set No communi cation to the bat tery applicable only for the model with Smart Bat tery and not with capacitors Over Temperature bit 9 set was de tected and the charging of the battery was inter rupted Requires a newer second hard ...

Page 43: ...group TwinCAT v3 1 0 PC or CX x86 x64 ARM Beckhoff BAPI v1 Beckhoff P24Vxxxx Beckhoff CP903x card PCI ISA Beckhoff CX2100 09x4 models e g CX2100 0904 or CX2100 0914 Smart Battery CX2900 0192 The APC devices that come supplied with Beckhoff Industrial PC support the Smart protocol and can be configured with the Windows UPS service Tc2_IoFunctions IO ...

Page 44: ...64 ARM Beckhoff BAPI v1 Beckhoff P24Vxxxx Beckhoff CP903x card PCI ISA Beckhoff CX2100 09x4 models e g CX2100 0904 or CX2100 0914 Smart Battery CX2900 0192 The APC devices that come supplied with Beckhoff Industrial PC support the Smart protocol and can be configured with the Windows UPS service Tc2_IoFunctions IO 7 5 4 E_UpsCommStatus Status of communication with the UPS hardware TYPE E_UpsCommSt...

Page 45: ...s Status of the power supply TYPE E_UpsPowerStatus PowerUnknownStatus PowerOnLine PowerOnBattery END_TYPE Name Value Meaning PowerUnknownStatus 0 The status of the power supply is unknown PowerOnLine 1 Mains power supply Battery power supply 2 Battery power supply Requirements Development en vironment Target platform UPS hardware PLC libraries to be integrated cate gory group TwinCAT v3 1 0 PC or ...

Page 46: ...ed off Yellow Output voltage Uout is above 28 8 V Table 11 Diagnostics LED DIAG LED Color Description DIAG Off No input voltage Uin present UPS is not initialized White No battery module or capacitor board found White Red or White Green flashing White timer for shutdown is active Red in case of discharge Green intentional shutdown Red No input voltage Uin present UPS is not being charged Blue Red ...

Page 47: ... module can be ordered from Beckhoff Requirements T20 TORX screwdriver C9900 U015 replacement battery module with 15 Wh Replace the battery as follows 1 Switch off the power supply to the UPS 2 Unscrew the two M4 screws and pull the battery module out of the UPS 3 Push the replacement battery module into the UPS until the contacts click into place 4 Fasten the battery module with two T20 screws ð ...

Page 48: ... the UPS from the power supply before clean ing Clean only the housing of the UPS Use a soft moist cleaning cloth for this Make sure that the ventilation slots of the device are always free and do not clog up The following cleaning agents and materials are unsuitable and may cause damage corrosive cleaning agents solvents scouring agents hard objects ...

Page 49: ...s how to disassemble the UPS and thus remove it from the DIN rail Shut down the industrial PC connected to the UPS so that the UPS is switched off Requirements Switch off the power supply Dismantle the UPS as follows 1 Push the UPS upwards ð As soon as you push the UPS upwards the lower springs of the DIN rail adapters give way This allows the UPS to be released from the top edge of the DIN rail 2...

Page 50: ...ules CU9900 U015 and CU9900 U030 replacement battery modules for CU8130 UPS modules from Beckhoff Automation GmbH Co KG are marketed exclusively to corporate customers According to the German law on batteries BattG we take old batteries back and pass them on to a disposal company The transport costs are covered by the sender Send the old battery with the note For disposal to Beckhoff Automation Gm...

Page 51: ...n the scope of supply Connection 2 x 9 pin plug push in Power supply 24 V DC 15 20 Capacity 15 Wh Output voltage min 24 V DC Max output current 5A Max power input 120 W Max power output 110 W Fuse electronic 5 A Operating system requires Windows Embedded Standard 7 Windows 7 Professional Windows 7 Ultimate or Windows 10 IoT Enterprise Diagnostics LED 1 x UIN 1 x UOUT 1 x DIAG Table 14 Technical da...

Page 52: ... plate made of black anodized aluminium for mounting the UPS on the control cabinet wall suitable for CU8110 0120 CU8130 0120 and CU8130 0240 C9900 P950 Spare connectors for the power supply of the CU81xx UPS series Two 9 pin connectors with push in connection for cables with a cross section of 0 14 mm to 1 5 mm or AWG26 to AWG16 C9900 K552 connecting cable USB 2 0 A B 3 m C9900 K553 connecting ca...

Page 53: ...omponents there Beckhoff Headquarters Beckhoff Automation GmbH Co KG Huelshorstweg 20 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 e mail info beckhoff com Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging services support design programming and commissi...

Page 54: ...gnment 15 Table 6 Power supply X102 connection on left side 16 Table 7 Power supply X102 right hand connection 16 Table 8 Required cable cross sections and strip lengths 20 Table 9 Diagnostics LED Uin 46 Table 10 Diagnostics LED Uout 46 Table 11 Diagnostics LED DIAG 46 Table 12 Technical data dimensions and weights 51 Table 13 Technical data general data 51 Table 14 Technical data environmental co...

Page 55: ...pply X102 16 Fig 8 CU8130 0120 dimensions 17 Fig 9 CU8130 0120 with mounting plate optional dimensions 17 Fig 10 Schematic wiring of a CU8130 0120 UPS 20 Fig 11 Example of a connection via UPS OCT with a CU8130 0120 UPS and a CX5240 Embedded PC 21 Fig 12 Connection example when using the second USP output U2out for an additional Control Panel 22 Fig 13 Example of a connection via USB with a CU8130...

Page 56: ......

Page 57: ...Beckhoff Automation GmbH Co KG Hülshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff en CU8130 0120 ...