Mounting 

1.

 

The four enclosure mounting screw locations are found within the four lid screw holes. 

2.

 

To ensure the IP68 rating is kept - cable glands used for cable entry must be of IP68 rating. 

3.

 

Route mains and low voltage output cables via different cable entries. 

4.

 

Use bushes and cable glands rated to UL94 HB minimum. 

Mains Power Up 

1.

 

Attach correctly rated mains cable (minimum 0.5mm

2

 [3A], 300/500Vac). 

2.

 

Apply mains power. Check for 12.0Vdc on load outputs. Check green Mains LED is illuminated on 
the modules. 

3.

 

Disconnect mains power.  

 

Load Output

 

1.

 

Attach correctly rated load cable(s). Note polarity. 

2.

 

Re-apply mains power. Check green Mains LED is on. 

3.

 

Verify load is operating correctly. 

 

 

M

AINTENANCE

   

 

There is no regular maintenance required of this PSU.

 

 
If the output of the PSU fails the cause of the failure should be investigated e.g. short circuit load.  The 
fault should be rectified before restoring power to the PSU.  The fuse(s) may need to be replaced.  
Ensure the correct fuse rating and type is used.  

 

 

 

D

ISPOSAL OF 

P

RODUCT AT 

E

ND OF 

L

IFE

 

 

 

This  product  falls  within  the  scope  of  EU  Directives  2012/19/EU  Waste  Electrical  and  Electronic 
Equipment (WEEE). At the end of life, the product must be separated from the domestic waste stream 
and disposed via an appropriate approved WEEE disposal route in accordance with all national and local 
regulations. 
 

 

For more information see: www.recyclethis.info 

 

 
 
 
 
 
 
 
 
 
 

 
 

 