Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200500_03C  Dec 2016                      ©2016 ELMDENE INTERNATIONAL LTD  

S

PECIFICATION 

(O

UTPUT

 

Voltage 

13.4 – 14.2Vdc (13.8Vdc nominal) on mains power 
10.0 – 12.3Vdc on battery standby 

Max load current 

See Model Specification Table overleaf 

Ripple 

150 mV pk-pk max 

Load output Fuse 

See Model Specification Table overleaf 

Overload 

Electronic shutdown until overload or short circuit removed 
(under mains power only) 

 

S

TANDBY 

B

ATTERY

 

 

Battery Type 

12V Valve Regulated Lead Acid 

Battery Capacity 

See below under enclosure size. 

 

L

OCAL 

I

NDICATORS

 

 

MAINS LED (Green)  

Mains present  

FAULT LED (Red)

*

 

Fault present: Output fuse fail 

*

Not 4A or 5A

 

  

 

S

IGNALLING 

O

UTPUTS

 

 

Lid Tamper  

N/O volt free contact (See Table for rating). 
Note: Contact open when lid opened by normal means 
(TAMPER ACTIVE condition). 

 

F

USED 

O

UTPUTS 

(

OPTIONAL

 

Model 

G1380xN-s 

G1380xN-2-s 

G1380xN-4-s 

G1380xN-8-s 

No. of fused outputs 

Fuse Value 

See table 

overleaf 

2 x (max load 

current / 2) 

4 x (max load 

current / 4) 

8 x (max load 

current / 8) 

 

M

ECHANICAL

 

 

Model 

G1380xN-y-A 

G1380xN-y-B 

G1380xN-y-C 

G1380xN-y-F 

Enclosure Dimensions

  

w x h x d (mm) [external]

 

230 x 200 x 80 

355 x 330 x 80 

330 x 275 x 80 

380 x 230 x 75 

Battery Capacity 

 1 x NP7 (8Ah)  1 x NP17 (18Ah)  1 x NP17 (18Ah) 

1 x NP7 (8Ah) 

Weight (kg) 
(Excluding Battery) 

1, 1.5, 2, 3A 

1, 2, 3A  4, 5A  1, 2, 3A  4, 5A 

1, 2, 3A 

2.0 

3.9 

4.3 

3.3 

3.7 

3.5 

 

E

NVIRONMENTAL

 

 

Temperature – Operating 

-10 to +40°C (operating) 75% RH non-condensing 

Temperature - Storage 

-20 to +80°C (storage) 

 
 
 
 