22
Installation-Programming C402-C404
8.5 SUPERVISED SIREN OUTPUT
Siren Output
Output voltage
24V
⎓
Maximum available current
550mA (C402)
500mA (C404)
End of line resistor
3300
Ω
Protection fuse (F3)
5x20 – 250V F500mA
8.6 FIELD OUTPUT
Field Output
Output voltage
24V
⎓
Output voltage when AC is missing and the
batteries resistance is high
22,3V
⎓
Output drop and control panel turn off voltage
18.5V
⎓
Maximum ripple on output voltage
15mV
Maximum available current
550mA (C402)
500mA (C404)
Protection fuse (F1)
5x20 – 250V F500mA
8.7 FAULT RELAY OUTPUT
Fault relay output
Type of contact
SPDT form C – dry contact
Maximum applicable voltage
30V
⎓
Maximum current
1A resistive load
8.8 DISTRIBUTION OF CONSUMPTIONS
Distribution of consumptions (1.6 A max)
Current drawn only by the card of the control panel
120mA (C402)
140mA (C404)
Available current at the field output
550mA (C402)
500mA (C404)
Available current at the supervised siren output
550mA (C402)
500mA (C404)
Available current at the detection circuits for the
conventional detectors
80mA (C402 – 2 detection circuits)
160mA (C404 – 4 detection circuits)
Available current for batteries recharge
300mA
8.9 MR402, MR404 OPTIONAL MODULES - OUTPUT WITH RELAY
Outputs with relays
Type of contact
SPDT form C – dry contact
Maximum applicable voltage
30V
⎓
Maximum current
1A resistive load
Symbol
Meaning
Direct current voltage
Refer to the installation manual