4
Installation-Programming C402-C404
1 GENERAL DESCRIPTION
1.1 INTRODUCTION
The fire detection control panels C402 and C404 control respectively up to 2 and 4 independent zones with a
maximum of 32 devices per zone. Each circuit is considered as an zone and can be included or excluded via a keypad
command.
The control panel has two outputs: a general alarm siren output, which is armed with at least one zone in alarm, and
another one for general fault, which is armed when a fault condition is verified on the control panel or in the zone.
The general alarm siren output can be included or excluded via the keypad. Further relay outputs
are available on the
optional relay card.
It is possible, independently for each zone, to decide whether to notify the alarm condition when one (single knock) or
more (double knock) devices detect an alarm.
C402 and C404 control panels can internally host two 12V 7.2Ah batteries (RB06 type). The batteries are not supplied
with the product.
1.2 OPTIONS
Optional modules
•
MR402 auxiliary card with relay output (for C402)
•
MR404 auxiliary card with relay output (for C404)
1.3 CE MARKING AND ACCOMPANYING DOCUMENTATION
According to the requirements of EN54, the “CE” marking is included and contains all required data:
is a trademark of URMET S.p.A.
Via Bologna, 188/C - 10154 Torino - Italy
11
0051-CPR-0338
DoP n. 0051-CPR-0338
C402
Control and indicating equipment for fire
detection and fire alarm systems buildings
EN 54-2: 1997 + A1:2006
EN 54-4: 1997 + A1:2002 + A2:2006
100-240 V
∼
-15/+10%, 50/60 Hz, 1 A
Vout: 26V
⎓
, ± 10%, 1.6 A
Options with requirements list:
7.8 Output fire alarm device
7.12 Co-incidence detection
0051
11
0051
is a trademark of URMET S.p.A.
Via Bologna, 188/C - 10154 Torino - Italy
11
0051-CPR-0337
DoP n. 0051-CPR-0337
C404
Control and indicating equipment for fire
detection and fire alarm systems buildings
EN 54-2: 1997 + A1:2006
EN 54-4: 1997 + A1:2002 + A2:2006
100-240 V
∼
-15/+10%, 50/60 Hz, 1 A
Vout: 26V
⎓
, ± 10%, 1.6 A
Options with requirements list:
7.8 Output fire alarm device
7.12 Co-incidence detection
0051
11
0051