5.1 Jumper description
Door holders delay: place the
Jumpers on J2 to associate
the Door holders release
delay according to the table:
Place the jumper 5-6
on J2 to set the door
check function.
Note:
The control panel provides a total of 300 mA for all external loads. The partitioning of the
equipment on the various outputs is provided by the installer
.
6 Installation
For environments with maximum height of the
covering/ceiling up to 6 metres, position the
appliance on the ceiling, leaving a space of 1
metre from the wall on which the front door is
present (see the figure shown to the side).
For environments over 6 metres tall, but not
greater than 12 metres, use an external
detector which is connected to the C/302
control module and installed on the ceiling.
The C/302 control panel shall be installed at
a height equal to half of the covering/ceiling
height, leaving a space of 1 metre from the
wall on which the front door is present. In such
case, use an appropriate bracketing to secure
the installation horizontally (see the figure
shown to the side).
Note: in all cases, the C/302 Control
Panel should always be positioned
horizontally.
Delay Pos.
jumper
1-2 3-4
0 s
15 s
30 s
Door check
5-6
Active
Off
Jumper present
Jumper assent
Door
Door
Soffitto - Ceiling
Muro
laterale
Side
Wall
000083
12 m
6 m
C/302
BP212
1 m
Porta-Door
Soffitto - Ceiling
Muro
laterale
Side
Wall
000084
6 m
C/302
1 m
Porta
Door