4 Specifications
Main supply rated voltage:….........................................230 V
Main supply rated frequency:….................................... 50 Hz
Appliance max. input:....................................…………. 100 mA
Protection fuse 230 V (F1):……………………...............Delayed fuse 5x20 T250 mA
Stabilized secondary voltage ……………………...........24 VDC 300 mA
Protection fuse 24 VDC (F2):........................................ Delayed fuse 5x20 T500 mA
Smoke detector:………………………………………...... Optical tyndall effect
Heat detector:………………………………………......... Alarm temperature: 60°C
Optical alarm:………………………………….…….…… Red warning lights located on 2
sides, 1 lamp 24 V 2 W
Acoustic alarm:………………………………………...... Buzzer
Working temperature:……………………….................. -10°C…..+50°C
Alarm free exchange relay contacts:…….....…………. 1A max. 30 VDC
Battery:…………………………...........................……. 2 Batteries of 12 V - max 1,2 Ah
Battery recharging current:……………………………. 120 mA
Casing material:……………………………….............. ABS self-extinguishing UL94-V0
Colour:…………………………………………………… RAL 7032
Sizes (mm):……………………………………………. ..283 (L) – 113 (P) - 71 (H)
Weight:…………………………………………………... 700 g
Protection degree:…………………………………..….. IP 32
NOTES:
•
Connect a residual thermal-magnetic circuit-breaker upstream of the
appliance.
•
To ensure the appliance protection against accidental infiltration of water and
dust, use a cable gland with a minimum protection degree IP32 and a
flammability class 5V.
•
For connecting the appliance to the electric main, use a power cord ensuring
a double insulation.