background image

2 / 2

HRN-33 / 

HRN-63

HRN-34 / 

HRN-64

HRN -35

HRN-37 / 

HRN-67

HRN-34

Umax

Un

Umin

15-18

LED   

LED U

t

t

H

H

HRN-33, HRN-37

>

Umax

Un

Umin

15-18

LED   Un

  LED U

H

H

t

t

HRN-35

>

Umax

Un

Umin

15-18

25-28

LED   Un

    LED U

H

H

t

t

<t

<t

HRN-63,HRN- 64, HRN-67

Umax

Un

Umin

LED>Un

15-18

t

t

Warning

Technical parameters

Devices line HRN-3x and HRN-6x are constructed to be connected into 1-phase main or 
DC circuits (according to types, it is necessary to observe voltage ranges) and must be 
installed in accordance with regulations and standards applicable in a country of use. 
Installation, connection, setting and servicing can be done only by a person with an 
adequate qualifi cation who has read and perfectly understood this manual and function of 
the device. The device contains protections against over-voltage peaks and disturbances in 
the supply main. To assure correct function of these protections, there must be front-ended 
suitable protections of higher degree (A, B, C) and according to a standard switched devices 
(contactors, motors, inductive loads etc.) must be screened. before installing it is necessary 
to  make  sure  that  the  device  is  not  energized  and  main  switch  is  in  position  OFF.  Do  not 
install device to sources of excessive electromagnetic disturbances. By correct installation 
of the device, ensure perfect air circulation so the maximal operational temperature of the 
device is not exceeded when operated 24 hours a day with higher ambient temperature. Use 
screwdriver width approx. 2 mm to install and set the device. Please keep in mind that it is a 
fully electronics device while mounting it. Correct function of the device is also depended 
on the type of transport, storing and handling. In case you notice any damage, deformation, 
malfunction or missing piece, do not install the device and claim it at the seller. The device 
can be dismounted, recycled or stored at protected dumping-place after its lifetime.

Function

Supply and measuring

Terminals:

Voltage range:

Power input:

Max. dissipated power 

(Un + terminals):

Upper level (Umax):

Bottom level (Umin):

Max. permanent:

Peak overload < 1 ms:

Time delay:

Accuracy

Setting accuracy (mech.):

Repeat accuracy:

Dependance on temperature:

Tolerance of limit values:

Hysteresis 

(from fault to normal):

Output

Number of contacts:

Current rating:

Breaking capacity:

Inrush current:

Switching voltage:

Output indication:

Mechanical life:

Electrical life (AC1):

Other information

Operating temperature:

Storage temperature:

Electrical strength:

Operating position:

Mounting:

Protection degree:

Overvoltage cathegory:

Pollution degree:

Max. cable size (mm

2

):

Dimensions:

Weight:

Standards:

A1 - A2

    AC 48 - 276 V /                                        AC 48 - 276 V /       AC 24 - 150 V / 

        50 - 60 Hz              DC 6 - 30 V               50 - 60 Hz                50 - 60 Hz

  AC max. 1.2 VA /   DC max. 1.2 VA /   AC max. 1.2 VA /   AC max. 1.2 VA /

             0.5 W                       0.5 W                        0.5 W                         0.5 W

              4 W                            4 W                           6 W                           4 W

    AC 160 - 276 V         DC 18 - 30 V        AC 160 - 276 V        AC 80 - 150 V

   30 - 95 % Umax   35 - 95 % Umax     30 - 95 % Umax    30 - 95 % Umax

          AC 276 V                  DC 36 V                 AC 276 V                  AC 276 V

         AC 290 V                   DC 50 V                 AC 290 V                  AC 290 V

adjustable, 0 - 10 s

5 %

< 1 %

< 0.1 % / °C (°F)

5 %

2 - 6 % of adjusted value 

(only HRN-33, HRN-34, HRN-35, HRN-37)

16 A / AC1

4000 VA / AC1, 384 W / DC

30 A / < 3 s

250 V AC / 24 V DC

red / green LED

3x10

7

0.7x10

5

-20 °C to 55 °C (-4 °F to 131 °F)

-30 °C to 70 °C (-22 °F to 158 °F)

4 kV (supply - output)

any

DIN rail EN 60715

IP40 from front panel, IP20 terminals

III.

2

solid wire max. 1x 2.5 or 2x 1.5, 

with sleeve max. 1x 2.5 (AWG 12)

90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)

      62 g (2.2 oz.)         75 g (2.6 oz.)            86 g (3 oz.)            61 g (2.2 oz.)

EN 60255-6, EN 61010-1

Function HRN-63, 64, 67:
Monitoring  relay  line  HRN-6x  serves  to  monitor  levels  of  voltage  in  single-phase  or 
DC circuits. Monitored voltage is in the same time also supply voltage. It is possible to 
set two independayt levels of voltage. When Umax is exceeded, output is activated. 
In case voltage level falls below Umin, output is deactivated. This combination is 
advantageous  when  full  absence  of  supply  voltage  is  understood  as  faulty  state. 
as well as voltage drop in the frames of set level. To eliminate short voltage peaks 
in the main there is time delay which can be set in a range of 0 - 10 sec. Such delay 
applies in case of going from overvoltage to undervoltage. In case of returning from 
undervoltage to overvoltage this delay doesn’t apply. Thanks to changeover output 
contacts it is possible to reach various confi gurations and functions according to 
requirements or an application.

Legend:
Umax - upper adjustable level of voltage
Un - measured voltage
Umin - bottom adjustable level of voltage
15-18 - switching contact of output relay No.1
25-28 - switching contact of output relay No. 2
LED ≥ Un - green indicator light
LED   U - red indicator light
LED U> - red indicator light 
H - Hysteresis

Function HRN-33, 34, 35, 37:
Monitoring relay series HRN-3x monitores level of voltage in single - phase and DC 
circuits. Monitored voltage serves also as supply voltage. It is possible to set two 
independayt levels of voltage, when exceeded the output is activated. HRN-33, HRN-
34 and HRN-37 - in normal state the output relay is permanently switched. It switches 
off  when there is a below or above defl ection. This combination of connection of the 
output relay is advantageous when the full failure of supply (monitored) voltage is 
considered to be a faulty state in the same way as a decrease of voltage within the set 
level. Output relay is in both situations always switched off . Diff erently HRN-35 version 
uses independayt relay for each level, in normal state it is switched off . If the upper 
level is exceeded (for example overvoltage) 1 relay switches on, when the bottom 
level (e.g. undervoltage) is exceeded 2 relay switches. It is thus possible to see the 
particular faulty state. To eliminate short peaks in the main the time delay, which is 
possible to be set in range 0 - 10 s, is used. It functions when changing from normal to 
faulty state and prevents unavailing pulsation of the output relay caused by parasitive 
peaks.  Time  delay  doesn´t  apply  when  changing  from  faulty  to  normal  state,  but 
hysteresis (1 - 6 % depends on the voltage setting) apply. Thanks to changeover 
contacts it is possible to get other confi gurations and functions according to actual 
requirements of the application.

1x changeover / 

SPDT (AgNi / 

Silver Alloy)

1x changeover / 

SPDT (AgNi /

 Silver Alloy)

1x chang. for each 

level of voltage, 

(AgNi)

1x changeover / 

SPDT (AgNi / 

Silver Alloy)

Содержание HRN-33

Страница 1: ...odp t HRN 37 HRN 67 hl d nap t v rozsahu AC 24 150 V je mo no hl dat rove nadp t a podp t samostatn u v ech typ je nastaviteln prodleva 0 10 s pro eliminaci kr tkodob ch v padk i pi ek spodn rove nap...

Страница 2: ...ro instalaci a nastaven pou ijte roubov k e cca 2 mm M jte na pam ti e se jedn o pln elektronick p stroj a podle toho tak k mont i p istupujte Bezprobl mov funkce p stroje je tak z visl na p edchoz m...

Страница 3: ...RN 37 HRN 67 like HRN 33 monitors voltage in range AC 24 150 V it is possible to monitor level of overvoltage and undervoltage independently adjustable time delay for all types is 0 10 s to eliminate...

Страница 4: ...16 A AC1 4000 VA AC1 384 W DC 30 A 3 s 250 V AC 24 V DC red green LED 3x107 0 7x105 20 C to 55 C 4 F to 131 F 30 C to 70 C 22 F to 158 F 4 kV supply output any DIN rail EN 60715 IP40 from front panel...

Страница 5: ...troluje nap tie v rozsahu AC 24 150 V je mo n kontrolova rove nadp tia a podp tia samostatne u v etk ch typov je nastavite n oneskorenie 0 10 s pre elimin ciu kr tkodob ch v padkov i pi iek spodn rove...

Страница 6: ...10 s 5 1 0 1 C 5 2 6 nastav hodnoty len u HRN 33 HRN 34 HRN 35 HRN 37 1x prep nac 1x prep nac 1x prep nac pre 1x prep nac AgNi AgNi ka d rove AgNi AgNi 16 A AC1 4000 VA AC1 384 W DC 30 A 3 s 250 V AC...

Страница 7: ...kich typ w jest nastawialna zw oka czasowa 0 10 s dla eliminacji kr tkotrwa ych zanik w lub maksym w dolny prog napi cia Umin ustawia si w g rnego progu Umax 3 stanowa sygnalizacja LED wy wietla stan...

Страница 8: ...V DC 50 V AC 290 V AC 290 V ustawialna 0 10 s 5 1 0 1 C 5 2 6 nastaw wart tylko u HRN 33 HRN 34 HRN 35 HRN 37 1x prze czny 1x prze czny 1x prze czny AgNi AgNi AgNi 16 A AC1 4000 VA AC1 384 W DC 30 A 3...

Страница 9: ...z alacsony s t lfesz lts g figyel s szintjei k l n k l n be ll that k minden t pusn l 0 10 mp k z tti k sleltet s ll that be a r vid idej fesz lts g kies sek vagy t sk k kik sz b l s re az als fesz lt...

Страница 10: ...C 276 V DC 36 V AC 276 V AC 276 V AC 290 V DC 50 V AC 290 V AC 290 V ll that 0 10 s 5 1 0 1 C 5 2 6 a be ll tott rt khez csak HRN 33 HRN 34 HRN 35 HRN 37 1x v lt rintkez 1x v lt rintkez 1x v lt rintke...

Страница 11: ...ul AC 24 150 V este posibil monitorizarea nivelului supratensiunii i subtensiunii independent nt rzierea reglabil pentru toate tipurile este de 0 10 s pentru eliminarea c derilor sau a cre terilor de...

Страница 12: ...30 95 Umax AC 276 V DC 36 V AC 276 V AC 276 V AC 290 V DC 50 V AC 290 V AC 290 V reglabil 0 10 s 5 1 0 1 C 5 2 6 din valoarea reglabil numai pentru HRN 33 HRN 34 HRN 35 HRN 37 1x contact 1x contact 1x...

Страница 13: ...Czech Republic HRN 33 HRN 37 HRN 34 HRN 64 HRN 63 HRN 67 HRN 35 HRN 3x HRN 6x HRN 33 HRN 63 AC 48 276 V HRN 34 HRN 64 HRN 33 DC6 30V 24 V HRN 35 HRN 33 HRN 37 HRN 67 AC 24 150 V 0 10 Umin Umax 3 LED 2...

Страница 14: ...5 W 0 5 W 0 5 W 4 W 4 W 6 W 4 W AC 160 276 V DC 18 30 V AC 160 276 V AC 80 150 V 30 95 Umax 35 95 Umax 30 95 Umax 30 95 Umax AC 276 V DC 36 V AC 276 V AC 276 V AC 290 V DC 50 V AC 290 V AC 290 V 0 10...

Страница 15: ...ngs berwachung im Bereich AC 24 150 V unabh ngige berwachung von ber und Unterspannung m glich Verz gerung 0 10 s um kurzfristige Spannungsspitzen oder abf lle zu vermeiden Umin wird in von Umax einge...

Страница 16: ...instellbar 0 10 s 5 1 0 1 C 5 2 6 des eingestellten Wertes nur bei HRN 33 HRN 34 HRN 35 HRN 37 1x Wechsler 1x Wechsler 1x Wechsler AgNi AgNi AgNi 16 A AC1 4000 VA AC1 384 W DC 30 A 3 s 250 V AC 24 V D...

Страница 17: ...l de salida independiente para cada nivel de alimentaci n as es posible por ejemplo con la salida de sobretensi n conmutar carga diferente que con la salida de subtensi n HRN 37 HRN 67 supervisa tensi...

Страница 18: ...1 C 5 2 6 de valor ajustado s lo HRN 33 HRN 34 HRN 35 HRN 37 1x conmutable 1x conmutable 1x conm para 1x conmutable AgNi AgNi cada nivel AgNi AgNi 16 A AC1 4000 VA AC1 384 W DC 30 A 3 s 250 V AC 24 V...

Отзывы: