Note the physical address on the device label.
Setting IP address
Necessary when connecting a PC or router to the integrated Ethernet interface. The IP address
can be allocated statically or dynamically via DHCP.
o
For static setting: Enter IP address in the ETS.
o
When setting via DHCP: Take IP address from the router's address table.
Commissioning M-bus
If M-bus is activated, the connected measurement points are automatically scanned and
allocated according to their secondary addresses. Primary addressing is not supported.
Commissioning the wireless M-bus
Wireless M-bus measurement points cannot be scanned; they can only be received. The
measurement points are recognized and allocated by means of their secondary addresses.
6 Appendix
Simplified Declaration of Conformity
Hereby Elka Elektronik GmbH declares that the radio system type
KNX measurement point gateway, art. no. 13516140
corresponds to the directive 2014/53/EU. The complete text of the EU Declaration of Conformity
is available under the Internet address:
www.elka.de/compliance
Legal Notice
This product incorporates open source software components covered by the terms of third party
copyright notices and/or license agreements. Details for addressing are contained in the
technical data.
6.1 Technical data
External supply
Rated voltage
DC 24 V ±10 % SELV
Power consumption
6.5 VA
Power supply
Max. 50 W / 2 A
Connection mode
Screw terminal
Protection class
III
Ambient conditions
Ambient temperature
-5 ... +45 °C
Storage/transport temperature
-25 ... +70 °C
Fitting width
72 mm / 4 modules
Weight
approx. 175 g
Network communication
IP communication
Ethernet 10/100
IP transmission rate
10 / 100 Mbit/s
IP connection mode
RJ45 socket
Number of measurement points
M-bus and wireless M-bus
max. 20
S0
2
D0
1
M-Bus
Rated voltage, M-bus
DC 36 V SELV
Transmission rate
2400 bit/s
Connection
Screw terminals
wireless M-Bus
Reception frequency
868.0 ... 868.6 MHz
Operating modes
T1 / S1
Antenna connection
SMB socket
8/9
KNX Metering gateway
82594604
05.02.2016