background image

SINUS PENTA 
PENTA MARINE 
IRIS BLUE 

 

STO FUNCTION  

APPLICATION MANUAL 

 

20/

27

 

 

5.  VALIDATING THE OPERATION OF A SAFETY FUNCTION 

 
Safety  Standards  EN  IEC  62061  and  EN  ISO  13849  require  that  the  final  assembler  of  the  machine 
validates the operation of the safety function with an acceptance test.  

 

The acceptance tests must be performed: 
At  initial  start-up  (commissioning)  of  the  safety  function  or  installation  of  a  new  drive  unit  in  place  of  an 
existing one, 
At each periodic annual test of the safety function, 
After any changes (wiring, components, settings, etc.) related to the safety function, 
After any changes related to the CPU CONTROL BOARD ES927 of the drive, 
After any maintenance activity related to the safety function, 
After any Test Result FAIL during the STO acceptance test procedure and subsequent decommissioning 
of ES927 damaged board and replacement with a new one. 
 

5.1.  Acceptance Test Reports 

Signed acceptance  test reports must be stored  into the Instruction’s Manual of the machine. The report 
shall  include  documentation  of  start-up  activities  and  test  results,  references  to  failure  reports  and 
resolution  of  failures.  Any  new  acceptance  tests  performed  due  to  periodic  annual  test  (once  a  year), 
changes, maintenance and decommissioning 

shall be logged into the Instruction’s Manual of the machine. 

Section 5.3 Performing the Acceptance Test includes the template of the Check List for 

‘STO Acceptance 

Test

’, as a guide for a test report. 

 

5.2.  Authorized Person 

The acceptance test of the safety function must be carried out by an authorized person  having adequate 
expertise  and  knowledge  of  the  safety  function.  The  test  must  be  documented  and  signed  by  the 
authorized person. 
 

5.3.  Performing the Acceptance Test 

The drive is working with motor torque applied to motor during the acceptance test. 
The following template shall be included in the 

Instruction’s Manual of the machine incorporating the motor 

drive. 

 

 

WARNING

 

Speed and torque applied during the acceptance test need to be compliant 
with acceptable working conditions of the application where the drive is 
installed. 

 

 

WARNING

 

The Safe Torque Off function does not cut off the mains voltage and auxiliary 
circuits from the drive. Therefore, maintenance work on electrical parts of the 
drive or the motor can only be carried out after isolating the drive system from 
the mains supply. 

 

 

NOTE

 

The Safe Torque Off function can be used for stopping the drive in emergency 
stop situations. In the  normal operating mode, it  is not recommended to stop 
the  drive  by  using  the Safe Torque Off function. If a running drive is stopped 
by using the Safe Torque Off function, the drive will trip and stop by coasting. 
If this is not acceptable, e.g. causes danger, the drive and machinery must be 
stopped using the appropriate stopping mode before using this function.

 

 

 

NOTE 

Note  concerning  permanent  magnet  motor  drives  in  case  of  multiple 
IGBT power semiconductor failure: 

Due  to  the  possible  DC  output  voltage  present  for  certain  multiple  IGBT 
failures,  in  spite  of  the  activation  of  the  Safe  Torque  Off  function,  the  drive 
system  can  produce  an  alignment  torque  which  maximally  rotates  the  motor 
shaft by 180/p degrees (p is the pole pair number).

 

Содержание IRIS BLUE

Страница 1: ...damages caused by improper erroneous and irrational uses Elettronica Santerno is responsible for the device in its original setting Any changes to the structure or operating cycle of the device must b...

Страница 2: ...ACING AND DIAGNOSTICS 22 6 1 COMMISSIONING 22 6 2 MAINTENANCE 22 6 3 DECOMMISSIONING 22 6 4 DISPOSAL 22 6 5 ALARM MESSAGES GENERATED BY THE DRIVE 23 7 COMPONENTS FOR STO APPLICATIONS 24 7 1 ES927 BOAR...

Страница 3: ...7 Figure 4 Installation example of a Sinus Penta S75 S80 7 Figure 5 Example schematic diagram of STO function with Safety Relay PILZ PNOZ X3 for safe power cut off 9 Figure 6 Example schematic diagra...

Страница 4: ...isolation may be necessary The STO is a function that allows stopping the motor in a safe way if externally demanded The STO function removes power from the motor by disabling the PWM commands from t...

Страница 5: ...arine and Iris Blue product lines share the same sizes and physical appearance as the Sinus Penta the only differences lie in the control functions and the selection of power conversion components opt...

Страница 6: ...SINUS PENTA PENTA MARINE IRIS BLUE STO FUNCTION APPLICATION MANUAL 6 27 Figure 2 Installation example of a Sinus Penta S64 S70 S2 R2 T2 T1 R1 S1 U1 V1 S64 S65 S70...

Страница 7: ...ON APPLICATION MANUAL SINUS PENTA PENTA MARINE IRIS BLUE 7 27 Figure 3 Installation example of a Sinus Penta S74 Figure 4 Installation example of a Sinus Penta S75 S80 S75 includes two power supply un...

Страница 8: ...he STO function disables the control voltage of the power semiconductors of the drive output stage thus preventing the inverter from generating the voltage required to rotate the motor see diagram bel...

Страница 9: ...reset when after deactivating the Emergency Stop the RESET push button is pressed in this case 13 14 and 23 24 are closed and 24Vdc power supply is restored to the ENABLE A and ENABLE B inputs of the...

Страница 10: ...SINUS PENTA PENTA MARINE IRIS BLUE STO FUNCTION APPLICATION MANUAL 10 27 Figure 6 Example schematic diagram of the STO function with simple emergency pushbutton...

Страница 11: ...e work on electrical parts of the drive or the motor can only be carried out after isolating the drive system from the mains supply NOTE The Safe Torque Off function can be used for stopping the drive...

Страница 12: ...SINUS PENTA PENTA MARINE IRIS BLUE STO FUNCTION APPLICATION MANUAL 12 27 2 ES927 CONTROL BOARD Figure 7 Top view of ES927 M9 Pin 1 Label S ENABLE B M4 Pin 2 Label 15 ENABLE A LEDs and Display...

Страница 13: ...ARINE IRIS BLUE 13 27 Figure 8 Front view of terminal blocks for ES927 Figure 9 LEDs and Display on ES927 LED L9 SCK2 LED L8 SCK1 LED L2 PWM ENABLE LED L1 RUN LED L6 5V LED L5 15V LED L4 15V Display M...

Страница 14: ...uts is de energized the STO function is active and stops the drive the drive can start only after the STO inputs have been energized and the drive faults if any have been reset CAUTION The STO functio...

Страница 15: ...N APPLICATION MANUAL SINUS PENTA PENTA MARINE IRIS BLUE 15 27 The STO function breaks out the PWM logic signals at ES927 control board level therefore it is completely independent of the power size of...

Страница 16: ...s performed by the board CPU under firmware control This is an additional verification of the STO related signals and the result if failing is reported as alarm A140 When the alarm trips the drive ope...

Страница 17: ...e LIGHT OFF If at least one of the internal and intermediate PWM signals are not at the proper logic level or at least one of the related components are NOT correctly working one or both the Diagnosti...

Страница 18: ...ardware proof test circuit based on redundant logic gates reads the dedicated Enable commands for the PWM signal buffers inserted in the two channels of the STO function circuit The Enable command of...

Страница 19: ...signal logic level configuration is correct and all related components are correctly working then the Diagnostic LED PWM Enable L2 is LIGHT OFF Test Result FAIL Diagnostic LED PWM Enable L2 is LIGHT...

Страница 20: ...afety function must be carried out by an authorized person having adequate expertise and knowledge of the safety function The test must be documented and signed by the authorized person 5 3 Performing...

Страница 21: ...he drive hardware manual Close the disconnector and switch the input power on Test the operation of the STO function as specified by the DT01 test procedure DT01 Periodic Proof test Diagnostic LEDs Sy...

Страница 22: ...put terminals do not need any maintenance Maintain the drive as per the instructions given in the drive hardware manual 6 3 Decommissioning If the ES927 board or wire sets are replaced inside the modu...

Страница 23: ...ult Cause What to do A140 Torque Off not Safe Internal hardware logic or firmware failure User could try to reset the alarm In case of persistent alarm board ES927 is damaged board decommissioning and...

Страница 24: ...llation environment Pollution degree 2 or better according to IEC 61800 5 1 Do not install in direct sunlight and in places exposed to conductive dust corrosive gases vibrations water sprinkling or dr...

Страница 25: ...Manufacturer New Elfin Part Number 020PTFASRK 020GE02 7 4 Switch Proposal to be used with Prevention of Unexpected Start up Function Implemented with STO for STO Application Type A lockable selector...

Страница 26: ...C 61508 EN 61800 5 2 EN ISO 13849 1 are listed below Data apply to all sizes of inverter of Sinus Penta Iris Blue and Penta Marine line IEC 61508 EN ISO 13849 SIL PFHG HFT SFF DC Category PL CCF 3 2 3...

Страница 27: ...oted channels D Dangerous failure rate per hour of a channel in a subsystem equal to 0 5 DD Detected dangerous failure rate per hour of a channel in a subsystem sum of all the detected dangerous failu...

Отзывы: