INSTRUMENT PROGRAMMING
Operation parameters, completely modifi able from front keypad. Access to these is protected by a password that prevents random changes or modifi cations by
unauthorised persons.
Accessing parameters (con
fi
guration):
1.
press the PRG and SET buttons together
for more than 5 seconds and the display will show "00", password required;
2.
use the buttons
or
to scroll the numbers until displaying "
11
" (Password for accessing parameters);
3. confi rming with
SET
, the fi rst modifi able parameter will appear on the display.
Modifying parameters
After displaying the parameter, proceed as follows:
1. use the buttons
or
to scroll the parameters to the one to be modifi ed. Scrolling is accompanied by lighting up of an icon on the display, representing the
parameter category. Alternatively, press the
PRG
button to display a menu of the categories or parameters for quickly accessing the family of parameters to be
changed;
2. scroll the menu with the buttons
and
and the codes of the various parameter categories (see "Summary of operation parameters") are displayed, together
with lighting up of the corresponding icon (if present);
3. on accessing the category, press
SET
to go straight to the fi rst parameter of the selected category (if no parameter is visible, pressing the
SET
button will
have no eff ect);
4. it is possible to continue consulting the parameters or return to the categories menu with the
PRG
button;
5. press
SET
to display the value associated with the parameter;
6. increase or decrease the value respectively with the buttons
and
;
7. press
SET
to temporarily save the new value and return to the display of the parameter. Repeat the procedure from step 1 or step 2;
8. if the parameter has subparameters, press
SET
to display the fi rst subparameter;
9. press the buttons
or
to view all the subparameters;
10. press
SET
to display the associated value;
11. increase or decrease the value respectively with the buttons
or
;
12. press
SET
to temporarily save the new value and return to the display of the subparameter code;
13. press
PRG
to return to the display of the parent parameter.
Saving new values assigned to parameters
To permanently save the values of the modifi ed parameters, press the
PRG
button for more than
5 seconds
, thus exiting the parameter modifi cation proce-
dure. It is possible to cancel all the parameter modifi cations, temporarily stored in RAM, and return to "normal operation" by not pressing any button for 60 seconds,
thus allowing the parameter modifi cation session to expire for TIMEOUT.
Attention
:
If the modifi cation session expires for timeout, the parameters will not be not restored.
If the power to the instrument is switched off before pressing the
PRG
button, all changes made to the parameters and temporarily saved will be lost.